Loading...
Ordinance 1986-016 Adopts Standard Building Code 1985 Edition including Appendices ORDIPIRNCF. N0. 16-86 AN ORDINANCE OF THE VILLAGE OF NORTH PALM BEACH, FLORIDA, AMENDING CfIAPTFR 6 OF THE VILLAGE OF IIORTH PALM BEACH CODE, THE BUILDING CODE FOR THE VILLAGE, BY ADOPTIfJG BY REFERENCE THERETO THE STANDARD BUILDING CODE, 1985 EDITION, INCLUDIIJG APPENDICES B, C, E, I, 0 AND ,R, THERETO SETTING FORTH 1 AMENDMENTS TO SAID STANDARD BUILDING CODE. BE IT ORDAINED BY THE VILLAGE COUNCIL OF NORTH PALM BEACH, FLORIDA: Section 1._ Section 6-16 of the Village of North Palm Beach Code is hereby amended to read as follows: "Sec. 6-16. ADOPTED BY REFERENCE---Under the authority of Section 553.73, Florida Statutes, the Village of North Palm Beach hereby adopts by reference hereto, the Standard Building Code, 1985 Edition, including P,ppendices B,C,E,I, 0 and Rand the recommended amendments of the Building Code Advisory Board of Palm Beach County, as the building code for the Village. There has been for at least t.en days last past and shall be during the time that this code is in effect, three copies of such code and. recommended amendments kept available for public use, inspection and examination." Section 2. Section 6-17 of the Village of North Palm Beach Code ' is hereby amended to read as follows: "Sec. 617. AMENDMENTS, CORRECTIONS AND ADDITIONS---The following amendments, corrections, and additions to the recommended amendments of the Building Code Advisory Eoard of Palm Beach County, including Appendix 3, are hereby made and adopted; said amendments, corrections and additions being set forth herein with reference to and prefaced by the Section number and title of said amendments, as follows: Section 103.1.1.--Amend. to read: 7. Install or replace gasoline, fuel, oil, bottled gas, oxygen, nitrous oxide, or similar liquified or gaseous storage tanks, pumps, and related equipment, above or below ground in a capacity of more than five (5) gallons. Section 103.6.2. SPECIAL INSPECTOR. Amend to read: 103.6.2.1. 'fl;e Building Official shall require the contractor of a commercial building of 5,000 square feet or more of floor area on the ground floor or an apartment house of thirty (30) or more apartments to pay the l'illaoe of North Palni Beach an hourly inspection fee, monthly on demand. The certification of the number of hours to be charged shall be ma~'e by the ' Building Official monthly. The hourly rate for the inspection fee shall be established yearly by the Village f4anager prior to November 1st of each fiscal year. 1 103.6.2.2. FACTORY BUILT HOUSING, amend to read: Factory built housing, as defined in the Florida Statute 553, Part IV, shall be inspected by the Building Department during the placing of the buildings on the foundations. This inspection shall cover the unloading and erection of the building components and the hook-up of the utility lines. An hourly inspection fee, in addition to the regular building permit fee, shall be charged by the Village to the Contractor for this inspection time. The certification of the number of hours inspection time to be charged shall be made by the Building Department. The hourly rate for the inspection fee shall be established yearly by the Village Manager prior to 1 November of each fiscal year. Section 103.7.4. SCHEDULE OF PERMIT FEES, amend to read: 103.7.4. For all building, electric, plumbing, mechanical and gas work requiring a permit as set forth in Section 103.1, a fee shall be paid as required at the time of obtaining the permit in accordance with the schedule and other provisions contained herein. A permit shall not be issued or valid until a fee as prescribed under this Section has been paid. A separate permit and fee shall be required for each structure or improvement. At the time of filing for a permit, a minimum of 30% of the estimated permit fee shall be paid. Permit fees shall be based on the estimated value and multiplied by the following percentage rates. Primary permits will include the cost of all sub permits provided the necessary information is completely detailed on the plans and the cost of such improvement is included in the estimated value. 1 2% $0.00 - $10,000.00 plus 1% $10,001.00 - $100,000.00 plus .5% $100,001.00 - $500,000.00 plus .25% $500,001.00 - $1,000,000.00 plus .125% $1,000,001.00 and up (or fraction thereof) The minimum permit fee shall not be less than $20.00. Moving building - $100.00 Residential driveways, approaches and sidewalks - 20.00 Building demolition - 100.00 Construction trailers - 20.00 A reinspection fee of $20.00 may be charged for each reinspection made due to the rejection of work, or due to the fact that work was not ready at the time specified in the request for inspection, or failure to call for inspection. Payment of such fee must be made prior to the reinspection. Plan filing fee - 30% of estimated permit fee upon filing. Deduct amount from actual fee if permit is obtained within 4 months from approval date; if not, filing fee is not refundable. ' Major change fee after plans are approved and permit issued -- $250.00 fee but in no case more than the original permit fee. Major plan rechecking fee - 2nd and additional check lists - 10% of permit fee for checking service each time rechecked. Processing Fee - In addition to the fees required under this Article, the owner of the real property upon which improvements are to be constructed shall pay a processing fee of $5.00 for furnishing copies of the printed statement required by Section 713.135, Florida Statutes; however, no such additional fee need by obtained in the event the applicant and the owner are the same. Section 103.9.2.1. REQUIRED FOR CERTIFICATE OF OCCUPANCY. Add new paragraph. A certificate of occupancy shall not be issued by the Building Official until a certified survey of the property, locating all existing improvements and property lines for said property shall be furnished to the Village. Section 105 - Delete Section - See Contractors Board Ordinance. Section 107 - Delete Section. Section 305. EXCEPTIONS TO RESTRICTIONS IN FIRE DISTRICT. Add new paragraph 11 as follows: 11. One and two family dwellings and private garages may be erected on Type VI wood frame construction in zoning classifica- tion R-1 and R-2 only providing such buildings are set back from ~, side and rear property lines at least ten (10) feet. Section 2402.8. CONTROLS. Add new paragraph: I ~; When activated, all fire alarm pull stations, smoke and heat ~ ~i detectors except local alarm type and fire sprinkler flow I~ switches shall recall all elevators to the designated level. i Section 3. This Ordinance shall take effect immediately upon passage. ' PLACED ON FIRST READING THIS 23RD DAY OF OCTOBER 1986. PLACED ON SECOND, FINAL READING AND PASSED THIS 13TH DAY OF NOVEMBER 1986. (Village Seal) OR ATTEST: Village Clerk i I ! ~. UNIFORM, MINIMUM COUNTYWIDE AMENDMENTS TO THE STANDARD BUILDING CODE. 1983 EDITION REVIEWED AND RECOMMENDED BY THE BUILDING CODE ADVI80RV BOARD OF PALM BEACH COUNTY AND BUILDING OFFICIALS ASSOCIATION OF PALM BEACH COUNTY bc3.covds I ~ ~r TABLE OF CONTENTS Th• folloainp chaptrrs of th• Standard Building Cod• havr brrn amrndrd ~ CHAPTER 1 - ADMINISTRATION CHAPTER 2 - DEFINITIONS CHAPTER 4 - CLASSIFICATION OF BUILDINOB BY OCCUPANCY CHAPTER 'J - SPECIAL OCCUPANCY REOUIREMENTB CHAPTER 7 - FIRE PROTECTION REQUIREMENTS CHAPTER 9 - BPRINKLERB~ STANDPIPES ANO ALARM~8Y8TEM8 CHAPTER 10 - FIRE RESISTANCE STANDARD FOR MATERIALS AND CONSTRUCTION CHAPTER I1 - MEANS OF EORE$H CHAPTER 18 - MINIMUM DE8ION LOADS CHAPTER 13 - FOUNDATIONS CHAPTER 14 - MASONRY CONSTRUCTION CHAPTER 17 - WOOD CONSTRUCTION CHAPTER 88 - ALUMINUM CONSTRUCTION CHAPTER 30 - REFERENCED BTANDARD6 ADPENDIX 1 - BIDEWALK9 APPENDIX 2 - METAL UTILITY BUILDIN08 APPENDIX 3 - MINIMUM STRUCTURAL REOUIREMENTB FOR ONE AND TWO FAMILY DWELLINOB ATTACHMENT NUMBER 1 RTTACHMENT NUMBER 2 Vrrtical linrs in the margin indicate the subrtantivr chanp• to the 19BS rdition of the Standard Building Codr. Th• rrmaindrr of the trxt is as it apprars in the unamrndrd vrrrion and is intrndrd for convrnirncr of usrrs only. bc3.covds ~ i ~ CHAPTER 1 RDMINIBTRATION DELETE AND SU88TITUTE 301-TITLE AND SCOPH 101.1-TITLE Provisions in the following chapters and sections shall constitute and be known and may be cited as "The Standard Building Code" hereinafter referred to as "this Code". 101.E-CODE REMEDIAL 301. P.1 GENERAL. Thies Code is hereby declared to be remedial, and shall ba construed to secure the beneficial interests and purposes thereof - which era public safety, health, and general welfare - through structural strength, stability, sanitation, adequate light and ventilation, and safety to life and property from fire and other hazards Incident to the construction, alteration, repair, removal, demolition, use and occupancy of buildings, structures, or premises. 101.2.2 QUALITY CONTROL Quality control of materials and workmanship is not within the purview of this Coda except as specifically ast forth herein 301.2.3 PERMITTING AND INSPECTION Tha inspection or permitting of any building or plan by any ~urisdlction, under the requirements of this Coda shall not be construed in any court ar manner what so ever as a warranty of the physical condition of such building or the adequacy of such plan. No ,~uriadiction nor any employee thereof shall be liablw in tort or otherwise for damages for any defect or haxardaus or illegal condition or inadequacy in such building or plan, nor for any failure of any component of such building, which may occur subsequent to inspection or permitting. 101.3-SCOPE 101.3.1 APPLICABILITY The provisions of this Code shall apply to the construction, alteration, repair, equipment, use and occupancy, location, maintenance, removal and demolition, or every building or structure or any appurtenances connected ar attached to such buildings or structures. 101.3.2 FEDERAL AND STATE AUTHORITY The provisions of this Coda shall not be held to deprive any Federal or state wgency, or any applicable governing body having jurisdiction, of any power or authority which it had on the effective date of the adoption of this Code or of any remedy then exlsting for the enforcement of its orders, nor shall it deprive any individual or corporation of its legal rights as provided by law. 101.3.3 APPENDICES Appendices 1,2 and 3 included in this Code are net intended for enforcement unless specifically referenced in the adopting ordinance. 101.3.4 MAINTENANCE All buildings ar structures, both exlsting and new, and all parts thereof, shall be maintained in a safe and sanitary condition. All devices or safeguards which are required by this Code in a building when erected, altered, or repaired, ahall'be maintained in good working order. The owner, or his designated agent, shall be responsible for the maintenance of buildings and structures. bc1.86ds 1 REV. 8/28/86 101.4-BUILDING DEPARTMENT There is hereby •atabllahed a department to be called the Building Department and the parson in charge shall be known as the Pu d ding Official. 101.4.1 HUILDINO OFFICIAL QUALIFICATIONB The Building Official shall have at least 10 years experience or equivalent, as an architect, engineer, construction inspector, contractor, or superintendent of construction, or any combination of these, for 5 years of which he shall hwve been in responsible charge of work. He shall be appointed by the applicable governing body. He shall not be removed Prom office except far cause after full opportunity has been given him to be heard on specific charges before ouch applicable governing bndy. The Building Official shall be certified by either the Huilding Officials Raaociatlon of Florida, Southern Building Coda Congrera International, Council of American Building Officials or Florida Board of Codes and Standards as a Building Official, within 12 months of appointment. SOI.4.2 INSPECTOR gUALIFICATIONB The Building Official, with the approval of th• applicable governing body, may appoint such number of officers, inspectors, assistants and other employees as shall be authorized from time to time. A person shall not ba appointed as inspector of construction who has not had at least 5 years experience as a building inspector, engineer, architect, auperintentent, foreman or competent rnerhanic in charge of construction. The inspector appointed shall ba, within 12 rnontha of appointment, certified by either the Huilding Officials Association of Florida, Southern Huilding Code Congress International, Council of American Building Officials err Florida Saard of Codes and Btandarda as an inspector or be an Inspector- Trainee who must be certified by either of the above organizations within 5 years. Pu d ding Inspector-Trainee is defined err a person working under the direct supervision of the Building Official and whose duties are as follower Maintains a variety of office files and recorder pertaining to the Building and Zoning division and general inspection services and performs a variety of clerical services. Assists the general public, architects, engineers, contractors, builders, etc ., 1n applying far permits and obtaining information relative to codes and building and zoning procedures. Aids inspectors in checking building plena and specificationai assists in the issuance of permits. Performs minor Pield inspections under close supervision and review by certified inspect ore. Obtains information form the tax assessor and other agency departments regarding legal descriptions and ownership of properties, buildings, and other structures relative to inspections, inrtallation, and condemnation proceedings. Additionally performs related work as required. 101.4.3 DEPUTY BUILDING OFFICIAL Tha Building Official rosy designate as his deputy an ernployae in the department who shall, during the absence or disability of the Building Official, exercise all the powers of the Building Official. 101.4.4 REBTRICTION8 ON EMPLOYEES An officer or employee connected with the department, except one whose only connection is as a member of the board established by this Cods, shall not be financially interested in the furnishing of labor, material, err appliances for the construction, alteration, err maintenance of a building system, or in the making of plans or of specifications bc1.86ds 2 REV. 8/25/86 4~ ' thereof, unless he is the owner of such building. Such officer or employee shall not engage in any other work which is inconsistent with his duties or conflicts with the interests of the department. 101.4.5 RECORDS Thr Building Official shall keep, or cause tc. be kept, a record of the business of the department. The records of the department shall be open to public inspection. lO1.A.6.1 LIABILITY Any officer or employes, ar member of the Board of pd,juatrnenta and Rppeala, charged with the enforcement oP this Code, acting for the applicable governing body in the discharge of his duties, shall not thereby be held personally liable, and !a hereby relieved from all personal liability, for• any darnape that rosy accrue to persona or property as a result of any act required or permitted in the discharge of his duties. Rr~y suit brought against any officer or ernployas or member because of such ect perfor•rned by him or the orniaaion of same 1n the enforcement of any provision of this Coda, shall be defended by tics Department of Law until the Pinal termination of the proceedings. 101.4.6.E Any suit brought against any former employee of an agency for actions said ernployas rosy have taken in the lawful discharge of his duties while employed by said agency will be defended by the agency. 101.4.7 REPORTS The Building Official shall annually submit a report cavaring the work of the Building Department during the preceding year. 101.5-EXIBTINtl BUILDINGS 101.5.1 GENERAL Alterations, repairs or rehabilitation work may he roads to any rxisting building without requirirrp the building to comply with all the requirements of this Code provided that the alteration, repair or rehabilitation works conforrna to the requirements of this Code for new construction. The building Official shall determine the extent to which the existing system shall shall be made to conform to the requirernenta of this Coda for new construction. 101.s.P CHRNtlE OF OCCUPANCY If the occupancy classification of are existing building is changed, the building shall be made to conform to the intent of this Code as required by the Building Official. 101.6-SPECIAL HISTORIC BUILDINGS The provisions of thin Coda relating to the construction, altaratiorr, repair, enlargarnent, restoration, relocation or moving of buildings or structures shall not be mandatory for existing buildir~pa or structures identified and classified by State or local ,jurisdiction as an Historic Building when such buildings c.r structures are ,judged by the Building Official to be safe and in the public interest of health, safety and welfare general regarding any proposed corratructlor~, alteration, repair, enlargement, restoration, relocation or moving of buildings within firer districts. 1UP-POUER8 AND DUTIES OF TIDE BUILDING OFFICIAL 10P.1-RIGHT OF ENTRY 10P.1.1 Whenever rrecesaary to make an inspection to enforce carry of the proviafons of this Cade, or whenever the Building Official has reasonable cause to believe that there exists in any building or upon any premiaea any condition or code violation which makes such building or premiaea unsafe, dangerous or hazardous, the Puildinp Official rosy enter such building or premiaea at all bc1.86da 3 REV. 8/2S/86 ', , reasonable timra to lnsprct thr same or to perforce any duty imposed upon the Building Official by this Codr, provided that if such building or premises is occupied, ha shall first present proper credentials end request entryt and provided further, that if such building or premises is unoccupied, he shall first make a reasonably rffort to locate thr owner or othrr persons having charge or control of the building or premises and request entry. If such entry !a refused, the Building Official shall have recourses to every remedy provided by law to secure entry. 102.1.2 When the Building Official shall have first obtained a proper inspection warrant ar other remedy provided by law to secure entry, no owner or occupant ar any other pareses having charge, rare or control of any building or premises shall fail or neglect, after proper request ie made is herein provided, to promptly permit retry therein by the Building Official for the purpose oP inspection and examination pursuant to this Cade. 102.2-STOP WORK ORDERS Upon notice from tlye Puilding Official, work on any system that is being done contrary to the provisions of this Code or in a dangerous ar• unsafe rnannery shall immediately cease. Such notice shall be in writing and shall be given to the owner of the property, or to his agent, or to the person doing the work, or posted an ttre fob property in a conapicuoua place, and shall statr thr conditions under which work may br reaurned. Where an emergency exists involving an imminent threat to human life or healthy or• property of others, the Building Official shall not be required to give a written notice prior to stopping the work. 302.3-REVOCAYIUN pF PERMITS !02.3.1 M1IIREPRE$ENTATION OF pppLICATION Thr Building Official may revoke a permit or• approval, issued under the provisions of this Code, in rear there has been any false statement or rniarapr•esentation as Oo the material fact in the application er plans on which the porrnit ar approval was based. 302.3.E VIOLATION OF CODE RROVI$ION$ The may revoke a permit upon determination by thr that the construction, erection, alteration, demolition of the building for which the perms violation of, or not in conformity with, the Cade. Building Official Building Official repair, moving or t was issued is in provisionc of this 102.4-UNSAFE BUILDING All buildings c.r structures which are unsafe, unsanitary, or not pr^ovided witty adequate egress, or which constitute a fire hazard or are otherwise dangerous to human life, ar which in relation to existing use constitute a hazard to safety or health by reason of inadequate rnainter~ance, dilapidation, obr:olescencey or abandonment ar•e severally in contemplation of this section, unsafe buildings. All such unsafe buildings are hereby declared illegal and shall be abated by repair and rehabilitation or by demolition in accordance with the fallowing procedures 102.4.1 Whenever the Building Official shall find any building or structure ar portion thereof to bn unsafe, as set forth in this Code he shall, in accordance with established procedure for legal rioticea, give the owner, agent, or person in control of such building or structure written notice stating the defects thereof. This notice shall require the owner within a stated time either to complete specified repairs or improvements, ar to demolish and remove the building or structure or portion thereof. bc1.86ds 4 REV. 8/25/86 The Nuilding Official shall cause to be posted at each entrance to such building a notice statingt T'HI3 BUII_DINCa I9 UNBRFE RND ITS l1SF. OR OCCUPRNCY HRS BEEN PROHIBITED BY THE BUILDING OFFICIRL. Such notice sha]1 rernain posted until the required repairs are roads or demolition is completed. It shall be unlawful for any person, firm or corporation or its officers, agents, or ol;trer servants., to rernave such notice without written permission of the Puilding Official. or far any persan to enter the building except for L-he purpose of making the required repairs cm of demolishing xarne. 102.4.3 Ttre owner, spent or person in control strati have the right to appeal front the deciaian of the Building Officials as provided hereinafter, and to appear before the BuildinpBoard of Rd,justmentx ur~d Rppeala .rt a apselfisd time and place to show cause why tre should not comply with said notice. 102.4.4 In cases the owner^, agent, or persan in control cannot bs found witfrirr the stated tints limit, ar, if such owner, agent, or person in control shall fail, neglect, or refuse to comply with notice tc. repair, rehabilitate, or to demolish, and rernave said building or structure or ,portion thereof, the Building Official, after- Craving ascertained ttre cast, shall cause such building or str•uctur•e or• portion thereof, to be denroliahed, secured, or required ba rernain vacant. 102. 4. i5 Thy decision of the Building Official shall bs final in cases of errergcnry which, in his opinion, involve imminent danger to human life cm health or the property of others. He shall promptly cause such building „ structure, or portion thereof to hrr made safe or cauat. its reruoval. For• this purpose he may at ones} enter such structure or land on which 1t stands, or abutting land nr str•uctur•es, with such assistance and at such coat as he rosy deem necessary. He may order the vacation of ad.~acent structures and may require the proteetian of the public by appropriate fence or such r~t;her means as rosy be necessary, and for this purpaae may clc,se a public or private way. 10E.4.fi Costa incurrr=d under 102.4.4 and 102.4.3 shall be charged to the owner of the premiers involved. Tf the charges are not paid within a sixty day period following the billing notifical;ian sent by certified snail, the owner of the prernisea will be charged in the following manner: 1. The Building Official shall report the abatement to the governing body of Ctrs nuisance by the Building Official and the governing trody shall assess the entire coat of such vacation, demolition, or removal against the real property upon which such cost war; incurred, wtrirh assesarnent shall include but not he limited Lo all adntinirstr•ative caste, postal expenses, newap«per publicaticm, and shall constitute a lien upon such property auperior• to all others except taxes. 2. The Rgenry Clerk r:hall file such lien in the Countyss Official f2c>cor•d Book showing the nature of such lien, the amount thereof and an accurate legal description of the property, including the street addreBa, which lien shall be effective from the date of filing and recite the names of all persona notified and interested persons. Such lien shall bear interest from date of abatement of nuisance at the rate of 10 percent per annum for individual8 and 15 percent for corporate owners and sshall be enforceable ii' unsatisfied after the expir-atiorr of two years after the date of filing notice of such lien, as other liens may be ernforc•ed by the governing agency. bc1, Buds 3 REV. 8/23/86 102.3-REgl11REMEN7S NOT CDVERED BY CODE Any requirements rreressar^y for the strength, stability ar furrctiorrinp of err existing or proposed building ar structure, or for the public aefety, health and general. welfare, not specifically covered by this Code, shall be determined by the Building Official. 102.6-ALTERNATE MATERIALS AND METHODS (SEE ALSO ATTACHMENT NUMBER 21 The provisions of this Code are not intended to prevent the use of any mat erri::l or rnethrd of construction oat specifically prescribed by this Code, provided any such alternate has been approved by thcr Building Official. The Building Official shall approve arty such alternate>, provided he finds that the alternate for the purpo:;a intundNd is at least the equivalent of that prescribed in ttiir Code. ire quality, strength, effectiveness, fire resistanr.r•, durability and saferty. The Building Official shall require that ~ufficierrt widence or proof be submitted to suhatar~tiate a:~y claim rrrs.de regarding the alternate. 1 Oa-PE l.M x Tts 103.1.1 Any individual, partnership, firm, corporation or other business organization that is the awner or lessee of property„ who desirva that wank as: described below be performed on Bald owned or leased property, shall make provisions fcm an applicant, properly qualified under the laws and/or ordinances regulating the certification and licensing oP cantractars, awner-builder and leasee-~bcrilder, to file an application for -and obtain the required permit Pram tltct Building Official pricer to cornrnencing work for the following: 1. Ccn~rstruct, erect, enlarge, alter, move, remove, relocate, demnlicrh c,r c:hange the occupancy of any building, or portion thereof. ~. Tr~:aull, replace, r..r• r•nsurface roofing, c.r make repairs. 3. Install cr replace windows or doors including frames, ,jalousie, strmrn windows or stags, shutters, awnings, canopies, or almilar• itc:nra. 4. Erect or replace fer,cess, walla, signs, or sign structures. 3. ln:a all nr replace manta, towers far television or radio receivini!-franc>mittiny antenna extending mare than 10 ft above the last anchnr•ape, satellite dish antennas, flag poles, exterior lilthtirgl or similar items. 6. Install :,wirnminp pool, wading pool, or spas, above ar below ground, 2 ft ar mare deep or mare than 300 gallon capacity. 7. Tr~restWll ar replacagasoline, fuel, oil, battled gas, oxygen, nitrous oxide, or airnilar liquid or gaseous storage tanks, pumps, and related equipmerh, above or below ground in a capacity of more than 3 palluns. 8. Construct, replace or r•eaurfaee asphalt or concrete driveways, par•klrrp areas, hardatands, or sidewalks. 9. Install or replace docking rnaoring facilities for private or commerr.ial ra~tet^ rrat't, groins, seawalls, ,jetties, revetments, or airnilar struct-w^et. and far.ilitiea related thereto. 10. lr+e.tull, replace, or relocate fire sprinkler, fire alarm, smoke deter•tinn, or airnilar fire prevention and protection systems t+rxr r~•l;.rted aquipnrk:nt ar appurtenances. 11. C+uildin~ Jte~r~r.rits rosy not be required far replacement or repair work having value of leas than E1,000.00, providing hawevc±r• that; such work will not effect the structural integrity, fire rating, e><it access or egress rerauirernenta or violate arry other provision of this Code. In the case of raofir-~g repairs a permit may not be required for work work having a value of less than 55`.500.00. 103.1.2 1411Rt( AU'ffiOR'1ZED A general permit shall carry with it the right to install in the permitted building ar structure, or part thereof, he:atiny apparatus, olevator•s, sidewalk elevators, vaults, chutes, coal hales, lifts, cranes, derricks, steam power boilors, t;team, oil, gas or vapor engines, provided the same are bc1.86ds 6 REV. 8/23/86 103.1.3 ItJFUR1AATIUN Rf=pIJIRLfJ Each application for a perrnit, with thr raquircf fee, srhall b< filed with the Building Official on a form furnished for that purpose, and shall contain a general derscription of the• pf^aposed work and its location. The application E;Irall brz wigned by the owner, or his wuthorized agent. l'he application t}hall indicate the proposed occupancy of all parLa r..f tru l.,uildir+k bnd of that portion of the site or lot, if ar+y, rK?/ c,~vere<l by t;het building or structure, and shall contain s;+.rch ..•ih..-r ir,r,:,°rnaCic~re ae may be requir^ed by the Building Official. 103.1.4 TI1-+ff L1ttITFYT1fsW8 fir. appllcatian far a perrnit far any proposed work shall ht deerncd to haver been abandoned 6 months after the datEt of filing f~u• the permit, unless before then a perrnit is i~,vur,r). Or,u i.r• more extensions of tune for periods of not morEx than 90 rlaya each may be allowed by the Building Official tc.r tirE: application, provided the extenaian is requested in writing and ,juutifiaLle caurrEr is demonstrated. 103.2-Y%Rf~YJ1Nlt:~ iiYJll 5pE'[;Tfl1:A710Nti 103.2.1 REOl1YliEMENYti Whe» r•eyuirrd by the Building Official, two c,r~ sure E.:apies or specifications and of drawings drawn to scale with s,uffic:ient clarity and detail to indicate the nature and char~.acter af- bhc wE,rly shall accc.rnpsny the application for a permit. Sc,ch dr;,.;~,ingu ar-,d aper.ificationa shall contain i nfornrzxt i<•s,; ir, ti+r. fco•ar crf r,c.t e,t or c.therwi ae, as to the quality of r+,at~:,~c.,i., r,r+r;~r•Er ytaalfty iy essential to conform with thin Cc.de. ;".uch i„fc•rrnatic•n ahail be specific, and this Cade shall nob h~ cit.cd ., es a who1:~ ~»^ in 1,ar^t, nor shall the term "legal" or its eq+~iv.,la>ni. L.a usrvE;, <a a a,ur,stitute for specific inforrnaticm. 103.2.2 i-0l)Y)11'1CIWAL. DpTh the Building Official may require detailu, rrr:q;,rtutiara, ret:rusu diagrams, and ether data necessary to dr~st;•it+e i:f+t irret.:~fl«ti:,rr and basis of calculations and they shall herur• ti,c: sitrnatan°e c,f the person respansihle far the design. 103.2.3 DC.i31C3YJFR (F3Ef; ALk'10 A77ACHIdENT NUMBER 1 FOR ADDITIONAL RE~UIftEME:fJTi3 iatJO t:1(CEi~l'IONf31 10:3.2.3.1 fill .!rawia.sje., ~I,.,a:ificationa, and acec,rnanying data shall Lear th+~ r,;.ame, s:+iga:at+.u-r~, and addr^ess of the designer. 103. 2. 3. r h,.u suant to Chaptr3r 471 F. ti. errs Chapter 4B1 F. S. said nr:uiriner :Hall bE. Gither :w state registered architect or a state r.•nin+:.•-~~r.d r,r,~ir:~er• G.;r~ to be exempt therefrom) and shall per~for•rn ar;ly ±'~r.ase f.:>rvirer~, aarich he is authorized by law to perform. 103. 2. 3.s f`r~.~iidc.cr" 1`urthr:r that this code shell not be construed ka i.r•.r~ent tiny employee of an architect cm engineer from acCir•+, ir; ;.rry c:xpacit.y ,.andrrr the instruction, control, or supervisinra nP t.f:er arrY,itErr•t cn^ rrrgineer, cm prevent any person from acbiny a~, c. contraatw~ in the execution of work designed by an archite•r.t o;^ rn,girre;ar~ 103.2.4 fi'1RUt]YURAL FTN6 F"1RC RE13I137ANCE INTEGRITY plane far all b+-rilding•s e:hall incfirc,te how required structural and fire resistive irrtegrit:y will be maintained where a penetration of a requir-ed firt revtst~u,t wall, Ylc.or or• partition will be made for elecCric:al, nu:::har,irml, plurnlaing and conrrnunication conduits, pipes and sy.>t~~r+i, ar,u al~~r it+ctic-ate in sufficient detail how the fire integrity will b~~ ro~.intained where required fire resistant floors inter^uect; the e><tFJriar walls. br1.96ds % REV. 8/25/86 !03.2.5 BITE DRAWINGS Drawings shall show the location of the proposed building or structure and of every existing building ar structure on the site or lot. The Building Official may require a boundary Sine survey prepared by a registered surveyor. 103.3-EXAMINATION OF CONTRACT DOCUMENTS 303.3.1 PLAN REVIEW Ths Building OfPlcial shall axarnina or cause to be examined each application for a permit and the accompanying contract documents, consisting of drawings, specifications, computations and additional data, •nd shall ascertain by such examinations whether the construction indicated and described is in accordance with the requirements of thin Code and all other pertinent laws or ordinances. !03.3.2 AFFIDAVITS The Building Official may •ccapt a sworn affidavit frorn a registered architect or engineer stating that the plans submitted conform to the laws as to egress, type of construction and pensra6 arrangement and !f accornpanied by drawinpa showing the structural design, and by a statement that the plans and design conforrn to the requirements of this Cods as to strength, stresses, strains, loads and stability, he may without any examination or inspection accept such affidavit, provided the architect or engineer who made such affidavit agrees to submit to th• Building Official, copies of inspection reports as inspections are performed and upon completion of the structure a certification that the structure has been erected in accordance with the requirements of this Code. Where the Building Official relies upon such affidavit, th• architect or engineer shall assume full responsibility for the compliance with all provisions of this Code and other pertinent laws or ordinances. 103.4-I88UIN0 PERMITB 103.4.1 ACTION ON PERMITB The Building Official shall act upon an application for a permit without unreasonable or unnecessary deSay. If the Building Official is satisfied that the wc.rk described in an application for a permit and the contract docurents filed therewith conform to the requirements of this Code and other pertinent laws and ordinances, he shall issue a permit to the applicant. 103.4.2 REFUSAL TO ISSUE PERMIT If the application for a permit and the accompanying contract documents describing the work do not conform to the requirements of this Coda or other pertinent laws or ordinances, the Building Official shall not issue a perrnit'but shall return th• contract documents to the applicant with his refusal to issue such permit. Such refusal shall, when requested, be in writing and shall contain the reason for refusal. 103.4.3 SPECIAL FOUNDATION PERMIT When application for permit to erect or enlarge a building has been filed, the Building Official may, at hie discretion, issue a special permit for the foundation of such building. 103.4.4 PUBLIC RIGHT OF WAV R perrnit shall not be given by the Building Official for the construction of any building, or for the alteration of any building where said building is to be changed and such change will affect the exterior walls, bays, balconies, or other appendagee ar protections fronting on any street, alley or public lane, or for the placing on any lot or premises of any building or structure removed frorn another lot or premises, unless the applicant has made application et the office of the Director of Public Works for the lines of the public street on which he proposes to build, erect or .locate said buildings and it shall be the duty of the Building Official to sea that the street lines are not encroached upon except as provided for in Chapter 22. bc1.86ds 8 REV. 8/25/86 103.3-QURLIFICAYION OF APPLICANT Rpplicatian for permits will by accepted only from contractors currently licensed in their respective field and for whom no revocation or suspension of license is existing except that a sole owner may make application for permit and supervise the work in connection with the construction, maintenance, alterations, or repairs of a ample family or two family residence for his own use and occupancy and not intended far sale. The construction of more than one residence by an individual owner in any 12 month period shall be construed as contracting, and such owner shall then be required to be licensed as a contractor. Such licensed contractor or sole owner shall be held responsible to the Building Official for the proper supervision and conduct of all work covered tharaby. An owner or tenant of any building leasehold may make application for permit to repair or remodel any building when non-structural work is involved nat to exceed fS,000.00 in value within any 12 month period. 103.6-CONOY7YONS OF THE PERMIT 103.6.1 PERMIT INTENT R parrnlt issued shall ba construed to be a license to proceed with the work and shall net be construed as authority to violate, cancel, alter, or set aside any of the provisions of this Code, nor shall such issuance of a permit prevent the Building Official from thereafter requiring a corrvetion of errors in plans or in construction, ar of violation of this Code. Every permit issued shall become invalid unless the wark authorized by such permit is commenced within 6 months after its issuance, or if the work authorized by such permit is suspended or abandoned for a period of 6 months after the time the work is commenced. One or more extensions of time, for periods not morn than 90 days each, may be allowed for the permit, provided the extension is requested in writing and justifiable cause is demonstrated, and such extensions shall ba in writing by the Building Official. 103.6.2 SPECIAL INSPECTOR On new buildinpc ar additions of Type I or Typv II construction, on all mayor structural alterations, on concrete work where the design is based on f'c in excess of 3,000 pounds par sq in, and on buildings of area greater than 20,000 sq ft on buildings more than 2 stories in height, and an buildings and structures off unusual design ar methods of construction, the Building Official may require the owner to employ a special inspector for the inspection of the structural framework and such special inspector shall by present at all tirnea that work iv in progress on the structural frame. The Building Official may require a special inspector on pile driving. (Florida State Statute 553 requires a special inspector under certain circumstances.) Such special inspector shall be a registered wrchitect or engineer, or an employee oP either, or any other competent person or agency whose qualifications are approved by the Building Official who shall be responsible for the control of the materials and methods of construction. He shall be responsible for compliance with this Code wnd shall submit weekly progress reports of daily inspections to the Building Official. At the camplvtion of the construction work or project, the special inspector shall submit a certificate of compliance to the Building Official, stating that the work was done in compliwnce with this Code and in accordance with the permitted drawings and his duties shall end with the submission of ouch certificate. Final inapartian shall be made by the Building Official before a Certificate of Occupancy is issued. bc1.86ds 9 REV. 8/2S/86 In lieu of the above, the Building Official may accept a written certification by the designing architect or engineer that he has full supervision of the constructiont and in addition the Building Official may require that the supervising architect or engineer provide testing laboratory reports as to welding, concrete strength, etc., from a recognized and approved testing laboratory or similar facility. Upon completion the Building Official may require that the designing architect or engineer submit a certificate oP compliance, stating that all work was done in accordance with this Coda and the permitted drawings. 103.6.3 PLANS Whan the Building Official issues a permit, he shall endorse, in writing or by stamp, both sets of plena "Reviewed for Coda Compliance". One set of drawings so reviewed shall be retained by the Building Official and the other set shall be returned to the applicant. The permitted drawings shall be kept at the site of work and shall be open to inspection by the Building Official or his authorized representative. 103.'7-FEES 303.7.1 PRESCRIBED FEES A permit shall not be issued until the fees prescribed in this section have been paid. An arnandment to a permit shall not be issued until the additional fee, if any, due to an increase in the estimated coat of the building or structure, has been paid. 103.7.8 WORK COMMENCING BEFORE PERMIT ISSUANCE If any person commences any work on a building or structure before obtaining the necessary permit, he shall be sub,jvet to a penalty of double the permit fee. !03.7.3 ACCOUNTING The Building Official shall keep a permanent and accurate accounting of all permit fees and other moneys collected, the narnea of all persona upon whose account the same was paid, along with th• date and amount thereof. 103.7.4 SCHEDULE OF PERMIT FEES On all building, structures, or alterations requiring a building parrnit as sat forth in Section 103.1, a fee shall be paid as required at the time of filing application, in accordance with the fee sctredule establlatred by the governing authority. A reinspection fee of (10.00 may be charged far each reinspaction roads due to the rejection of work, or due to the fact that work was not ready at the time specified in the request far inspection, or failure to call for inspection. Rayment of such fee roust be made prior to the reinspaction. ' plan filing fee - 30% of estimated permit fee upon filing. Deduct amount from actual fee if permit is obtained within 4 months from approval datet if not, filing fee is not refundable. Major wnrt<ing drawing review fee - f100.00 deducted from permit fee if permit is obtained within 8 months from submission date. Major change fee after plans are approved and permit issued - +6280.00 fee but in no case more than the original permit fee. Major plan rechecking fee - 2nd and additional check lists - 10% of permit fee for checking service •ach time rechecked. 303.7.3 BUILDING PERMIT VALUATIONS If, in the opinion of the Building Official, the valuation of building, alteration, or structure appears to be underestimated an the application, permit shall be denied, unless the applicant can show detailed estimated cost to meat the approval of the Building Official. Rerrnit valuations shall include total cost, such as plumbing, electrical, rneehanieal equipment and other systems. bc1.86ds 10 REV. 8/28/86 103.8-YNSPECTYONS 103.8.1 E%I8TIN0 BUILDING Before isauinp a perrnit the Building Official may examine or cause to be examined any building for which an application has been received for permit to enlarge, alter, repair, move, demolish, or change the occupancy. He shall inspect all buildings and structures, from time to tiros, during and upon cornpletian of the work for which a permit was issued. He shall make a record oP every such examination and inspection and of all violations of this Code. 103.8.2 MANUFACTURERS RND FABRICATORS When deemed necessary by Lhe Building Official, he shall make wn inspection of rnateriala or assemblies at the point of manufacture or fabrication. He shall make a record of every such exarninatian and inspection and of all violations of this Code. 103.8.3 INSPECTION SERVICE Tha Building Official may rooks, or cause to bs made, the impactions required by thin section. He pray accept reports of inspectors of recognized inspection cervices provided that after investigation ho is satisfied as to their qualifications and reliability. R certificate called for by any provision of this Code shall not be based on such reports unless the same are in writing and certified by a responsible officer^ of such service. 103.6.4 YNBPECTIONB PRIOR TO ISSUANCE OF CERTIFICATE The Building Official shall inspect or cause to be inspected at various intervals all construction or work for which a perrnit is required, and a final inspection shall be made of every building or structure upon completion, prior to the lsauance of the Certificate of Occupancy. 103.8.8 POBTINS OF PERMIT Work requiring a building perrnit shall not cornrnance until the perrnit holder or hie agent poata the building permit card 1n a conspicuous place on the premises. The permit shall be protected from the weather and located in such position as to allow the Building Official to conveniently make the required entries thereon. This perrnit card shall be maintained in such position by the permit holder until the Certificate of Occupancy is issued by the Building Official. 103.8.6 REQUIRED INSPECTIONS The Building Official upon notification from the permit holder or his spent, shall make the following inspections oP buildinpa and such other inapectiona as may be necessary, and shall either approve that portion of the construction as completed or shall notify the permit holder or his agent of any violations to comply with this Coder 1. Foundation Inspections To be made after trenches are excavated and forms erected. 2. Frame Inspectionr To be made after the roof, all framing fir•eblocking and bracing is in place, all concealing wiring, all pipes, chimneys, ducts and yenta are carnplete. 3. Final Inspectionr To be made after the building is completed and ready for occupancy. 103.8.7 WRI77EN APPROVAL Work shall not be done on any part of a building er structure beyond the point indicated in each successive inspection without first obtaining the written approval of the Building Official. Such written approval shall be given only after an inapectlon has been made of each successive step in the construction as indicated by each of the faregeinp three inapectiona. 103.8.8 REINFORCING STEEL RND STRUCTURRL FRAMES Reinforcing at eel or structural frame work of any part of any building or structure shall not be covered or concealed without first obtaining the approval of the Building Official. bc1.86da 11 REV. 8/28/86 103.8.9 PLR8TER FIRE PROTECTION In all buildings where plaster is used for fire protection purposes, the permit holder or his agent shall notify the Building Official after all lathing acid backing is in place. Blaster shall not be applied until the approval of the Building Official has bean received. 103.9•-CERTIFICATE OF OCCUPANCY 103.9.1 BUILDING OCCUPANCY A new building shall not be occupied or a change made in occupancy or the nature ar• the use of a building or part of a building until after the Building Official has issued a certificate of occupancy. Said certificate shall not be issued until all required fire protection systems have been tested and approved. 103.9.2 ISSUING CERTIFICATE OF OCCUPANCY Upon completion of a building erected in accordance with the permitted plena, and after the final inspection the Building Official shall issue a certificate of occupancy stating the nature of the occupancy permitted. 103.9.3 TEMPORRRY OR PARTIAL OCCUPANCY A temporary or partial certificate of occupancy may be issued for a portion or portions of a building which rosy safely be occupied prior to final completion of the building. 103.9.4 EXISTING BUILDING CERTIFICATE OF OCCUPANLY A certificate of occupancy for any existing building may be obtained by applying to the Building Official and supplying the information and data necessary to determine compliance with this Coda for the occupancy intended. Where necessary, in the opinion of the Building Official, two sets of detailed drawings, or a general inspection, or both, may be required. When, upon examination and inspection, it is found that the building conforrnu to the provisions of this Code fur such occupancy, a certificate of occupancy shall be issued. 103.30-FLOOR LOADS 103.10.1 OCCUPANCY An existing or new building shall not be occupied far any purpose which will cause the floors thereof to be loaded beyond their safe capacity. The Building Official may permit occupancy of a building Por mercantile, cornrnercial ar industrial purposes, by a specific business, when he is satisfied that such capacity will not thereby b® exceeded. 103.10.2 STORAGE AND FACTORY-INDUSTRIRL OCCUPANCIES It shall be the responsibility of the owner, agent, proprietor or c.ccupant of Group S and Group F occupancies, or any occupancy where excessive floor loading is likely to occur, to ernplay a registered architect or engineer in computing the safe load capacity. All such computations shall be accompanied by an affidavit fr•orn the ar-chitect or engineer stating the safe allowable floor load on each floor in pounds per sq ft unlforrnly distributed. The computations and affidavits shall be filed as a permarier~t record of the Building Department. 103.ib.3 LOR08 IN EXCE88 OF CAPRCITY Ths owner shall not place, or permit to be placed, on any floor of a building a greater load than the safe load so determined. 104-TE8T8 The Building Official may require testa or test reports as proof of compliance. Required tests are to be made at the expense of the owner, or his agent, by an approved testing laboratory or other approved agency. bci.B6da 12 REV. 8/23/86 103-BOARD OF ADJUSTMENTS AND APPEALS 103.1-APPOINTMENT There is hereby established a board to be called the Board of Adjustrnents and Appeals, which shall consist of at least five rnernbers. The said Board shall be appointed by the applicable gover•nir~g body. 105. 2--APPEALS 105.2.1 GENERAL Whenever the Building Official shall reject or refuse to approve the mode or manner of construction proposed to be followed or materials to be used in the installation or alteration of a building or structure, or when it is claimed that the provisions off Chia Code do not apply, or that any equally good or rnor•e desirable form of installation can be employed in any specific rase, or when it is claimed that the true intent and meaning of this Code or any of the regulations thereunder have been mibrorrs:trued or Incorrectly interpreted, the owner of such building or structure, or his duly authorized agent, may appeal fr•orn the decision of the Building Official to the Board of AdjUfitfn~ntY and Appeals. Notice of appeal shall be in writing and filed within 90 days after the decision is rendered by the Euildir~g Official. Appeals shall be on forms provided by the Building Official. 105.2.2 UN$AFE OR DANDEROUB BUILDINDB In rasa of a building or• structure which, in the opinion of the Building Official, is unsafe ar dangerous, the Building Official may, in hie order, limit the time for such appeal to a shorter period. Such limitation shall be in writing to either the owner, applicant, agent, or^ representative as the case may be. 105.3-DECYBIONS 108.3.1 VARIANCES The Board of Adjustrnents and Appeals, when so. appealed to and after a hearing, may vary the application of any prevision of this Code to any particular case when, in its opinion, the enforcement thereof would do manifest injustice, and would be c:ontr^ary to the spirit and purpose of this Code or public interest, ar when, in its opinion the interpretation of the Building Official should be modified or reversed. 105.;5.2 ACYION 7-he board of Adjustrnents and Rppeals, shall, in every rase, reach a decision without unreasonable and unnecessary delay. If a decision of the Board of Adjustments and Appeals reverses or modifies s refusal, order, or disallowance of the Bullcllrig Official, or varies the application of any pr•oviaion of this Code, the Suildinp Official shall immediately take action in accordance with such decision. 105.3.3 bEL^ISIONB ARE FINAL Every decision of the Board of Rdjustrnents shall be final. Rppeals frarn the decisions of the Poar•d may be talcan by a writ of certiorari to a court of competent jurisdiction. 105.4--DOARD MEhIBERS AND PROCEDURES 105.4.1 St:CREl'ARY OF BDARD The Building Official shall act as Secr^etar-y of the Board of Rdjuatments and Appeals and shall make a detailed record of all its proceedings, which shall set forth the reasons far its decisiana, the vote of each mernber•, the absence of a rnernber, and any failure of a member to vote. 105. 4. 2 reg ~i 1 at i oria provisions pkOCEDURE The Board shall establish rules and for its own procedure not inconsistent with the of this Code. bc1.66da 13 REV. 8/25/86 106-VALIDITY If any sectic.n, subsection, sentence, clause, or phrase c.f this Code is far any reason held to be unconstitutional, such decision at~all riat affect the validity of the remaining portions of this Code. 107-VICII.ATIDNB AND PENALTIES Ar~y contractor, person, firm, corparatian or agent who shall violate a provision of this Cade, or fail to comply therewith, or with any of the requirements thereof, shall be guilty of a misdemeanor. Each such person shall be deemed guilty of a aeparata offense for each and every day or portion therec•f during which any violation of any of the provisions of this Code is cornrnitted or continued, and upon conviction of any such violation, such person shall be punished by a fine of not lees than 56 dollars nor more than SOO dollars, or by irnprisonrnent not exceeding 6 months, or by both such fine and imprisonment. bc1.86da 14 REV. 8/25/86 CHAPTER 2 DEFINITIONS 202-DEFINITIONS - tlUBBTITUTE OR ADD 7HE FOLLOWINOt AGENCY _ means same as applicable governing body. BASEMENT -- that portion of a building between Ploor and ceiling located so the vertical distance from grade to the floor below is equal to or leas than the vertical distance from grade to ce i 1 i rig. COVERED MALL Bl1ILDINO - a single building three stories or less in height enclosing a number of tanpnts and occupancies, such as anchor stores, retail, drinking wnd dining establishments, entertainment and arnuaernent facilities, offices and other similar uses wherein two or more tenants have a main entrance into one or more malls. FIRE RESISTANCE OR FIRE RESISTANCE RATING - the period of time a building or building component maintains the ability to confine a fire or continues to perform a given structural function ar both as deterrninad by testa prescribed in 1001.1. FLDOR tlRADE ~- minimum floor grade far residential building to be _,_________, inches above sidewalk or crown of road °_ .--- gradei commercial or industrial building to be _______,______ inches above the sidewalk or crown of road grade, unless satisfactory drainage, natural, or mechanical is provided. Mandatory flood plain, Fla. State Coastal Zone Nrotection Act, south Florida Water Management District elevation, or septic tank requlrernents, whichever is higher, must be adhered to. OOVERNINtl BODV means same as Applicable Governing Body. MARGIUEE -means a permanent roofed structure attached to and supported by the building. MEZZANINE - one or more intermediate levels between the floor and ceiling of a story. See 402.2.3. NONCOMBUSTIBLE BUILDING MATERIAL - a material which, meets either of the following requiramentsr 1. Materials which pass the test procedure set forth in RSTM E 136. 2. Materials having a structural base of noncornbuatible rnater•ials as defined in i, with a surfacing not more than 1/8- in thict< which has a flamespread rating not greater than 60 when tasted in accot•dance with ASTM E 84. The term noncornbuatlble does not apply to the flamespread characteristics of interior finish or trim materials. R material shall not be classed as noncombustible which is sub,~ect to increase in combustiblility or flamespread rating beyond the limits herein aatabllshad through the affects of age, moisture or othet• atrnoapheric conditions. OPENING -- an aperture in a wall, partition, floor, ceiling, or a roof. EXRMF~I.Ee window, dour, shaft, duct corridor, stairs, skylight. SCUPPER - an opening in a wall or parapet that allows water to drain from a roof. bc2.86ds 18 REV. 8/26/86 CHAPTER 4 CLASSIFICATION OF BUILDING BV OCCUPANCY 403-MIXED OCCUPANCY SEPARATION 403.1-GENERAL - ADD $UBBECTION 403.1.3 Tlrr~ following occupancies need not be separated from the user to which they are accesaory~ 1. Assembly rooms having a floor area of not over 750 sq. ft. 2. Administrative and clerical offices and airnilar rooms which, in the aggregate, do not exceed 25% of the floor area of the rna~or use when not related to Group N occupancies. 3. Rooms or spaces used for customary ctorape of nonhazardous materials in Sroup A - Assembly, Group B - Business, Group E - Educational, Oraup F -Factory-Industrial, Group M - Mercantile, and Group R - RBaidential, which in aggregate do not exceed one--third of the mayor occupancy floor area in which they are located. TABLE 403.1-AMEND AB FOLLOWB~ OCCUPANCY REPARATION REQUIREMENT8 Large Fl,aaembly------- Srnall Assembly------- Businasa------------- Educational --------- Fartary-Industrial -- Hazardous (Note 1) -- Institutional ------- Mercantile -_______-_ Reaider~tial _________________ ~ Storage (Note 1) ---_________ Rutomobile Parking Structures 1. If material being stored is hazardous in Section 408 and creates more of a hazard than - 4 Hour - 2 hour - 1 hour - 2 hour - 2 hour - 4 hour - 2 hour - 1 hour - 1 hour - 2 hour - 2 hour accordance with the display, the fire resistance separation shall be increased to 4 hours. 403.3-BEPARA7YON BEYWEEN TOWNHOUSES - SUBSTITUTE THE FOLLOWINO~ Each townhouse shall be considered a avparate building and shall be separated from ad,~oining townhouses by the use of separate exterior walls meeting there r•equirementa of Table 600 for zero clearance from property linen as required for the type of construction, or by a party wall, or when not more than three stories in height, rosy be separated by a single wall meeting the fallowing r•equir•ementst 1. Such wall shall provide not leas than a 2-hour fire r•esiatanee rating. Plumbing, piping, duet a, electrical or other bill lding services shall not be installed within or through the 2-hr_,ur wall. 2. Such wall shall be continuous from the foundation to ttre ~ander•aide of the roof sheathing. Tha roof sheathing shall be of nonrarnbustible material or exterior grade fire retardant treated wood, or one layer of 5/8 in Type X gypsum wallboard attached to the underside of the roof decking, far not less than a 4 ft, width on each aide of such wall. 3. Each dwelling unit sharing such wall shall be designed and cons.tr•ucted to maintain its structural integrity independent of tt~e unit on the apposite aide of the wall. EXCEPTIONt Said wall may be penetrated by roof and floor structural rnernbars provided that the fire resistance rating and the structural integrity of the wall is maintained. bc2.66da 16 REV. 8/23/86 406-EDUCATIONAL OCCUPANCY - GROUP E 406.2-SPECIAL PROTECTIVE REQUIREMENTS 406.2.1 - ADD SUSSECTION~ The following references to other protective requirements, as set forth ire this Code, shall apply 'to all areas classified as Group E accuparrcies. 1. Every heating appliance which produces an unprotected open flame shall be prohibited. 2. Where permanent rnation picture projectors using cellulose nitrate film are installed, booths shall be provided, as set forth in 404.11. 3. Rooms used 'for day care nurseries, kindarparten yr first grade pupils shall not be located above or below the floor of exit discharge. Roams used for second grade pupils shall not be located mare than one story above the floor of exit discharge. 4. Rules and regulations governing child care facilities in Palm beach County, Florida, adopted pursuant to Chapter 59- 1698, Special Acts, Lawa of Florida ag amended by Chapter 77- 620, Special Acts, Laws of Florida, with an effective date of November 1, 1984. 411-REF3IDENTIAL OCCUPANCY - GROUP R 411.1-SCOPE - RDD SECTION 411.1.3 See Section 506 for building more than four ataries in height. CHAPTER O SPECIAL OCCUPANCY REQUIREMENTS 506-BpECIAL PkOVISIONS FOR GROUP B ANO CiROUp R HIGH RISE BU I l.D I N09 506.1-SCOPE 506.1.1 - SUBSTITUYE THE FOLLOWINOt The requiramerrts of 6ectian 506 shall apply to all buildings more than 4 stories or 50 ft in helgtrt. Such building shall be provided with an approved autnrnatic sprinkler ayctem. 506.2-SMOKE DETECTION BYSTEM6 506.2.1 -ADD SUBSECTION At least one approved smoke detector suitable far the intended use shall be installed inr 1. Every rnechanlcal equipment, electrical, transformer, telephone equipment, elevator machine or similar ronrn. 2. In every elevator lobby. 3. Ir, the main return and exhaust air plenum of each air conditioning aystern serving morn than one story and located in a serviceable area downstream of the last duct inlet. 4. Eartr connection to a vertical duct or riser serving two or more stories from return air ducts or plenums or heating, and air conditioning system, except that in Group R occupancies, an srnake detector maybe used in each return air riser carrying eat more than 5000 cfm. and serving not more than 10 air• inlet openings. 5. See also 903.2 for smoke and fire detection systerna. 506.9-RRERB OF REFUGE (C0MPARTMEN7ATI0N) ALTERNATE - DELETE 606.11--A1.7ERNA7E$ PERMITTED - AMEND AS FOLLOWSt When a complete approved automatic sprinkler system complying bce.66du 17 REV. 8/25/86 with 506.10 is provided, the following modifications of Coda requirements are acceptablef 1. Fixed tempered glass may be used in lieu of operable panels for smoke control purposes. 2. The manually operated fire wlarm system required in the compartmented buildings is not required. 3. Spandrel walls, eyebrows and rompartrnentation are not required, however fire rasiatanca of the floors and ,juncture of exterior walls with each floor must be maintained. 4. 5nrokeproof enclosures may be omitted provided all required stairways are equipped with a dampered relief opening or an exhaust fan at the top and supplied mechanically with sufficient air to a minimum of 2500 cu. ft. per minute through the relief opening while maintaining a minimum positive pr•essur-e of O. 15 and a maximum of 0.50-in. water column relative to atmospheric pressure with all doors closed. Hctivatic•n of the mechanical equiprnant shall be in accordance with 1104.5.9.7. 5. Tire required fire resistance rating of vertical shafts other- than stairway enclosures and elevator hoistways may he reduced to 1-hear when sprinklers are installed within the shafts at alternate floors. 6. In Type I conctruction the fire rasiatanca of partitic•na, columns, trusses, girders, beams and floors may be reduced by 1•-hours, but no component ar assembly shall be lass than 1-hear. 508-RCCE88IBIL.ITV FOR THE PHYBICRLLY HANDICAPPED - SUBSTITUTE THE FOLLOWINO~ Puildinga and structures shall be made accessible to the physically handicapped in accordance with Chapter SS3, Part V, Flc•rida fit al;ute as amended and 8ectiarr 508.1. 5011.1-Ft!_UUYREO NUMBER OF ACCE88IBLE ELEMEN78 AND FACILY71E8 Where parking spaces and loading zones are provided, the number to be reserved for the handicapped shall be set forth in TABLE-~ 508.2 1'RRf<ING BPACEB AND PA88ENOER LORDING ZONES FOR HANDICAPPED. TABLE 508.E pRRKYNO BPACEB AND PASSENGER LOADING ZONES FOR HANDICAPPED Total tlpacsr or Zones Required Number to be Reserved for Handicapped up to 25 ~ 1 26 to SU 2 51 to 75 3 76 to 100 4 101 to 350 5 151 to 200 6 201 to 300 7 301 to 400 8 401 to 500 9 501 to 1000 2% of 7ota1 avers 1000 20 Plus 1 Fur Each 100 Over• 1000 CHAPTER 7 FIRE PROTECTION REOUIREMENTB 703-PROTECTION OF WRLL OPENINGS 703.3-PROTECTION OF OPENINGS IN INTERIOR WALLS bc2.86ds 18 REV. 8/25/86 703.3.4 - SUBSTITUTE THE FOLLOWING Fire dampers are not required under the following conditional 1. In buildings which da not require protected floor openings. 2. In duct syatema serving only ono floor and used only for exhaust of air to the outside and not penetrating a wall or partition having a required fire resistance rating of 2 hours or rnore or passing entirely through the enclosure for a vertical shaft. 3. Where branch ducts connect to return risers in which the air flow is upward and aubducts at least 22-in long are carried up inside the riser at each inlet. 4. See Standard Mechanical Code, 510 for additional exceptions. 706-RODE COVERINGS. 706,1-•tlENERAI. - SUBSTITUTE THE FOLLOWING Roof coverings shall be divided into the classes defined below, whose use within the Fire District shall be governed by the reyuirerner~ta of 302.2.4. .All Clwss R, 8 and C roof coverings shall be tested in accordance with ASTM E lOB. In addition, fire retardant treated woad roof coverirrga shall be tested in with RSTM D 2898. All roof coverings shall be installed in accordance with tine Palrn Beach County-wide Standard for the Installation of Roof Covarinps and other approved nationally recognized standards. 711-OUTTEkB AND LERDERB Gutters and leaders placed on the outside of buildings other than one or two-family dwellings, private garages, or buildings of type VI conatructian, shall be of nancornbustible material. See 1406 for parapet wall relief opening requirements and See the Standard Plumbing Cods for the sizing of interior leaders ar~d downspouts. CHAPTER 9 SPRINKLERS, STANDPIPES AND ALARM SYSTEMS 901-SPRINKLERS 901.6-ORRAOES - SU887ITUTE 7FiE FOLLOWINOt Approved automatic sprinkler syatema shall be provided in the following garagesr 1. Enclosed parking garages more than 4 stories or 50-ft in height or exceeding 10,000 aq ft per floor. 2. Repair garages 2 stories or more high, and exceeding 10,000 sq ft in a single floor area located below another occupancy. 3. One stcn^y repair garages exceeding 15,000 sq ft. 4. Basement or subbasement garages 5000 sq ft in area or repair garages in a cellar exceeding 2500 sq ft. 5. Garages used for the storage of commercial trucks and having an area exceeding 5000 sq ft. 6. Aus garages when used as passenger terminals for 4 or rnore buses or when used for bus storage ar loading of 4 or rnore buses. 901.7--OYIiER OCCUPANCY SPRINKLER REQUIREMENTS 901.7.2-GROUP I RESTRAINED - DELETE 901.7.3 Or•oup A - Larpe Assembly Occupancy 901.7.3.2.1-Group A Small Assembly Occupancy - ADD SECTION Rn approved automatic sprinkler system shall be provided in all small assembly occupancies having a capacity of 300 persons ar rnore, except churches, based on the minimum occupancy content in TADLE--1105.1. MINIMUM OCCUPANT CONTENT. bc2. 86da 19 REV. 8/25/86 CHAPTER !O FIRE RESISTANCE STANDARD FOR MATERIALS AND CONSTRUCTION 1004-CRLCULATED FIRE RESISTANCE - ADD BECTION~ 1004.1 Rppendix "P" is hereby made part of thla code together with the modification contained herein. 1004.1.2-TABLE P-3108.24 - SUBSTITUTE THE FOLLOWINOt TABLE P - 3108. 2A TIME AHSIONED TO WALLBOARD MEMBRANE81~2 DESCRIp7ION OF FINISH 1/2 in, fiberboard 3/8 in. plywood bonded with exterior glue 15/32 in. plywood bonded with exterior glue 19/32 in. plywood bonded with exterior plus 3/8 in. gypsum wallboard 1/2 in, gypsum wallboard 5/8 in. gypsum wallboard 1/2 in. type X gypaurn wallboard 5/8 in. type X gypaurn wallboard double 3/8 in. gypsum wallboard 1/2 + 3/8 in, gypaurn wallboard double 1/2 in. gypsum wallboard s 5 10 15 10 15 30 25 40 2B 35 40 1. 7heae values apply only when framing members are spaced 16 in nc. 2. On wood frarned walls, gypsum membrane board shall be installed with the long dimension parallel to frarninp mernbera withr all ,joints finished. 3. On wood frarned floor/ceiling aacernbliea, gypsum board shall be installed with the long dimension perpendicular to framinp rnembera and shall have all ~ointa finished. 1004. 1.3--TAHLE P-3108. 2C - SUBSTITUTE THE FOLLOWINOt TABLE P-3108.2C MEMHRRNEI ON EXTERIOR FACE OF WOOD STUD WALLS 8hrathinp Paper Exterior Finish 5/8 in.'fRG lumber Lumber siding 5/16 ire. exterior glue Sheathing paper Wond ahinglea & shakes plywood 1/2 irr. gypsum wallboard 1/4 in plyw.ext.type 5/8 in. gypaurn wallboard 1/4 in hardboard 1/2 in. fiberboard Metal siding Stucco on metal lath Maaanry veneer None 3/8 in. exterior plywood 1. Any combination of aheathirrp, paper and exterior finish listed may be used. bc2.86da 20 REV. 8/25/86 TIME IN MINUTES 1004.1.4-TABLE P-3108. 2D - BU88TITUTE THE FOLLOWINO~ TABLE P-330B.8D ------------------------------------------------------- FLOORINO OR ROOFING OVER WOOD FRAMIN01 Assembly Structural Bubfloor or Finish Flooring or Members Roof Deck Reroofing Hardwood or softwood flooring on building paper. Resilient flooring, parquet Floor Wood 15/32 1n.plywd, floor felted- or 11/16 in. synthetic-fiber floor T&0 softwood coverings, carpeting, or cerarnic file on 3/8 in. - thick panel-type underlay. Ceramic tale on 1 1/4 in. mortar bed. Roof Wood 15/32 in.plywd. Finish roofing material with or or 11/16 in, without insula- T60 softwood tion. 1. Thies table applies only to wood foist construction but 1s not applicable to wood trues construction. CHAPTER 11 MEAN8 OF EORE88 1103-ARRANOEMENT'AND NUMBER OF EXITS 1103.2-MINIMUM NUMBER OF EXITS 1103.2.3.4 -ADD EXCEPTIONS In Group 8 occupancies, one story only, and having a floor area leas than 2500 sq ft and a travel distance to an exit not exceeding 60 ft. EXCEPTIONt Ire storage spaces, such as rninl-warehouses, which meet all of the following requirement a, overhead doors may be used in lieu of aide swinging as required in 1114.1.1. 1. Spaces shall have a rnaximum floor area of 200 aq ft. 2. Buildings and grounds are continuously supervised. 3. Space is for dead atorap• only, occupancy of any other type is not permitted. 1104-8PECIAL EXIT REOUIREMENTB 1104.3-BMOKEPROOF ENCLOSURES 1104.6.9.3 - AMEND A8 FOLLOWB~ The vestibule calling shall be at least 20 1n higher than the door opening into the vestibule to serve as a smoke and heat trap and to provide an upward moving air column. The 20-in height requirement may be reduced proportionally if the minimum vestibule size described in 1104.5.9.2 is enlarged so as to maintain the same volurne in the smoke trap area above the door. In any case minimum ceiling height shall not be less than 7 ft 6 in. bc2.B6ds 21 REV. 8/25/86 1106-E%IT ENCLOSURE8 1106.2-E%TERIOR E%ITWAY STAIRS 1106.2.9 -ADD. SECTION All required exterlar exitway stairways shall be located completely outside the perimeter walls of the building. 111P-BTAIRWAV CONSTRUCTION 1112.3-TREADS AND RISERS !!12.3.2 -AMEND AS FOLLOWSr Trsada shall be of uniform width and risers of uniform height in any stairway between two floors. 1114-DOORS 1114.1-GENERAL 1114.1.1 -AMEND RS FOLLOWB~ Egreaa doors used as an exit door shall provide a clear opening of not less than 32-in wide and 6 ft B in high. The maximum leaf width of the door shall net exceed 4B in. Egreaa dears used 1n the exit access shall provide a clear opening of not leas than 29-in wide and 6 ft 8 in high. Egreaa doors shall be aide swinging type doors requiring a force of not more than 50 lb applied to the latch stile to fully open the door. E%CEPTIONt Doara within a dwelling or dwelling unit need not be aide swinging type, unless ouch doors open onto common corridors, common balconies or are required exits. 1114.1.2 -AMEND AS FOLLOWSt Every room or tenant space which is occupied by mare than 50 people ar 1n which the travel distance from the moat remote point to the entrance to the exit access exceeds 75 ft shall have net less than two egress doors located remote from each other and shall be so arranged and constructed to provide direct access in separate directions from any point ire the area served and to minimize the possibility that both may be blacked by any one fire or other emergency condition. Doors serving a room having an occupant load of 50 people or more shall swing in the direction of exit travel. In rooms or tenant spaces not meeting these conditions, only one egress door is required and it may awing into the room or tenant apace. 1115-RAMPS 1115.1-GENERAL 1115.1.3 - AMEND A8 FOLLOW8~ Where changes in elevations exist in access corridors, exits and exit outlets, ramps shall be used when the difference in elevation is less than 21 in. 1118-E%IT ILLUMINATION AND 820N8 1118.2--E%IT BIONB 1118.2.1 - AMEND AS FOLLOWSr All required exits shall be equipped with an approved exit sign in all occupancies except individual dwelling unite. 1121-OURRDRAILS - AMEND AS FOLLOWS A guardrail is a vertical protective barrier, not leas than 42 1r. in height. Open guardrails shall have rails or ornamental pattern such that a sphere, 6 in in diameter cannot pass through any bc2.86ds 22 REV. 8/25/86 opening. p bottom rail or curb shall be provided that will reject the passage of a sphere 2 in in diameter. Construction of guardrails shall be adequate in strength, durability and attachment for its purposes as prar4cribed in Chapter 12. EXCEPTIONB~ 1. Iri Group F -Factory Industrial and Group - 8 Storage occupancies not accessible to the public, open guardrails shall hnva intermediate rails or ornamental pattern such that a sphere 12 in in diameter cannot pass through any opening. 2. Guardrails need not be provided on the loading side of loading docks. 3. Guardrails within dwelling units shall be not less than 36 in in height. 4. Guardrails on a balcony immediately in front of the first r•ow of fixed seats and which are not at the end of an aisle may be 261n in height. Guardrails at the Pront edge of a balcony, loge or gallery where the aisle terminates shall be 42 in in height. 5. A guardrail shall net be required at the front of any stage. CHAPTER 18 MINIMUM DESIBN LOADS 1203-LIVE LOAD8 3203.6-ROOF LIVE LOADS 1203.6.1 -AMEND AB FOLLOWB~ Thr design roof live loads shall take into account the effects of occupancy and water but shall not be less than the minimum roof live loads as set forth in TABLE-1203.6 MINIMUM RODF LIVE LOAD, as amended. TABLE 1203.6 - AMEND AS FOLLOWB~ TABLE 1203.6 MINIMUM ROOF LIVE LOAD (Pounds prr squrrr foot of horizontal pro~retion) Roof 81opr Flat or rice leas than 4-in. per ft Arch ar dome with rise less than 1/8 of span Tributary Loadrd Arras !n 8quarr Frrt For Any Structural Mrmbrr O to 200 201 to 600 Ovrr 600 30 24 18 Rise 4-in.per ft to less than 12-in. per ft Arch or dome with rise 1/8 24 21 18 of span to less than 3/8 of span Rise 12-in.per ft and greater Rrch or dome with rise 3/8 18 18 18 of span or greater Rwnings except cloth covered 3 5 5 Oreenhouses,lath houses and 30 SO 30 agricultural buildings bc2.86dc 23 REV. 8/28/86 CHARTER 13 FOUNDATIONS 1302-FOOTINGS AND FOUNDATIONB 130$.$-BEARING CAPACITY OF BOIL - AMEND A8 FOLLOWSt 130$.2.1 Plain Concrete Masonry or Timber Footings. Footings shall be so that allow bearing capacity of the soil is net exceeded. If structural concrete, masonry or timber footings are used, they shall real on undisturbed or minimum 95% compacted soil of uniform density and thickness. 1302.2.2 Questionable Boils. Where the bearing capacity of the soil is not definitely known ar !s in question, the Building Official may require teats or other adequate proof as to the perrniasible safe bearing capacity at that particular location. Examinations of aubaoil conditions shall be made !n accordance with this cection 1302.2.8 at the expense of the owner. 1302.2.8 Boil Tests. All coil testa as required in 1302.2.2 shall be made in accordance with this section. Tests shall be cer•tlfied by an engineer so registered in the State of Florida. The certification shall bear the signature and seal of the engineer certifying the teat. 1302.$.8.1 All test shall be substantiated by data which is in accordance with A. S. T. M. or A. A. B. H. O. rtandarda and so noted. 130P.2.8.2 All sell testa shall contain the following rninimurn i n f arrn at i on r 1. Standard 15 ft penetration test to determine basic soil bearing capacity as required in TABLE-1302.2.9.4 shall be done in accordance with ASTM-D-1586 or ASTM-D-3441. 2. Soil profiles of the supplemental 10 ft augers as required in TABLE-1302.2.8.4 MINIMUM FREQUENCY OF SOIL TESTS, in order to verify uniformity of rnaterials. 3. The minimurn bearing value of the soil. 4. If deleterious material must f muck, silt, trash, etc.> be removed, the report shall contain detailed specifications for removal, disposal, classification of new fill material, teat control for backfilling and any other apeciel requirements as may be necessary. 5. If piling is recornrnended, it shall be so stated along with the appropriate piling specifications. 6. Should additional fill be required with in the boundary of the structure, specifications shall include the proper clearing, grubbing, placement and compaction of new fill. 1302.2.9.3 Frequency Of Tests. The frequency of teats shall ba in accordance with TABLE-1302.2.9.3 MINIMUM FREQUENCY OF BOIL TESTB. TABLE-1302.2.9.3 MINIMUM FREQUENCY OF BOIL TE8T81 TVPE LOT 10 FT AUOER2 !S FT PENETRATION Reaidentia141aolated 3 12 Residential up to 5 adJacent 4 1 every 3rd3 Residential over 5 ad,~acent5 2 1 every 4th3 All othera6 i. Frequency of tart per lot unless otherwise stated. 2. Located at each corner as rernote as passible frorn each other and within 4 ft of building line. bc2.86ds 24 REV. 8/25/86 3. Located at the approximate 4. Residential includes 1,2 a 5. Residential developments frequency to be determined by 6. Testing will be determined and practice. center of the structure nd 3 family dwellings. rosy test on a site basis with the the engineer. by accepted engineering standards CHAPTER 14 MASONRY CONSTRUCTION 1401-GENERAL 1401.6-WATER 8TOP - ADD BECTIONt Where exterior hollow masonry units bear on a concrete surface, a 1 1/2 in recess ar other effective water atop, as approved by the Building Official, shall be provided to prevent water intrusion. 1406-PARAPET WALLS 1406.1-DENERAL 1406.1.4 - AMEND A8 FOLLOWB~ Where required for roof drainage, a scupper shall be placed level with the roof surface in a wall or parapet. The scupper shall be located as determined by the slaps and the contributing area of the r•oaf. The exterior faceing or lining of a scupper rosy be metal and shall be the same as TABLE-114.3.2 VALLEY AND FLASHING MRTERIAL of the Palm Beach Countywide Btrndard for the Installation of Roof Coverings for the particular type of covering specified for the building. For other type materials follow rnanufacturaa apecificatians. 1406.1.4.1 A scupper shall be a minimum of 2 sq. in. for each 100 aq. in. of roof area. The minimum dirnenaion of a scupper shall be 3 in. 1406.1.4.2 When other means of drainage of overflow water is not provided, overflow scuppers shall be placed in walla or parapets oat lase than 2 in. nor more than 4 in. above the raof deck and shall be located as close as practical to required vertical leaders or downspouts or walls and parapets scuppers. An overflow scupper shall be a minirnurn of i sq. in. for each 100 sq. in. of roof area. 1409-MIBCELLRNEOUB DETAILS 1409.2-CHABE8 1409.2.4 -ADD SECTIONS Voids larger than 3 in outside diameter shall not be permitted in rninirnurn size exterior perimeter beams. CFiAPYER 17 WOOD CONSTRUCTION 1703-pRUTECTION ADAINBT DECAY AND TERMITES 1703.3 -• AMEND AS FOLLOWSt 8ILL8 AND BLEEPERS IN CONTACT WITH MASONRY. R11 wood coming in contnct with any concrete or masonry whether exterior or interior, shall be pressure treatrd or woad of natural decay resistance. 1703.4-SLEEPERS AND 8ILL8 ON CONCRETE SLABS - DELETE 1703.7-CLERRANCE BETWEEN BIDING AND EARTH - AMEND AS FOLLOWB~ Clearance between wood siding and earth on the exterior of a building shall be not less than 6 in. R11 siding shall be installed in accordance with the manufacturers specifications. bc2.86da 25 REV. 8/25/86 1703.11-RPPROVED PRECONBTRUCTION SOIL TREATMENT - ADD SUB-8ECTION 1703.11.1 Termite treatment of soil under slabs on grade under structures is required prior to placlnp concrete. 1707-VERTICAL FRAMING 1707.1-EXTERIOR WALL FRAMING - ADD EXCEPTION Studs in one-and-two story buildings shall be not less than 2 x 4 with the wide face perpendicular to wall. In three-story buildingar studs in first atary shall be not leas than 3 x 4 or 2 x 6. Studs shall be spaced not mor® than the fallowinpr Stud Suppartlnp roof Supporting 1 floor Supporting 2 floors 8iz• R tailing only roof R crailinp roof i cr.ilinp (in.) ------ (in.) -------'---°---° (in.) °--° °--_ __-___---- (in.) -_ _ 2X4 24 16 --__-_----°----- - 3X4 24 24 16 2X5 24 24 - 2X6 24 24 16 EXCEPTIONr 2 x 4 studs in all exterior walla or in any bsarinp partition shall be spaced not more than 16 in on canter. 1707.2-BRACING OF EXTERIOR STUD WALLS 1707.2.3 -AMEND A8 FOLLOW9r 8haathlnp shall be applied on the exterior walls oP Type VI buildings. 1708.1-CEILIND JOIST AND RAFTER FRAMING - ADD 8ECTIONB 1708.1.9 Show rafterc in eaves must be extended inside of the supporting rnembera approximately the awrne distance as the cantilever extended outward. 1708.1.10 Overhang at gable ends a maximum of 6 in era permitted without supporting structural members. 1708.4-ROOF SHEATHING 1708.4.1 - AMEND A8 FOLLOWBr All rafters and roof ,jaista shall be covered with sheathing as follower • 1. Lurnber~ solid sheathing of wood boards 5/8-in <net) minirnurn thick, or apace sheathing of wood boards 3/4-in (net) minimum thick. 2. Plywood applied in accordance with TABLE-1705.1 3. Fiberboard insulating roof deck not less than 1-in nominal thic{cneas. 4. Particle board shall not be used as roof sheathing. 1708.6-ANCNORADE OF ROOF FRAMING TO MASONRY WALLS - ADD 8ECTION 1708.6.1 All woad roof rnernbera shall be securely fastened to exterior walls with approved hurricane anchorc or clips. bc2.86ds 26 REV. 8/25/86 TABLE 1706. 6R - AMEND AS FOLLOWSt TABLE 1706.68-ALLOWABLE SPRN8 FOR PLYWOOD FLOOR AND ROOF SHEATHING CONTINUOUS OVER TWO OR MORE SPANS AND FACE GRAIN PERPENDICULAR TO SUPPORTS. Roof Floor Maximum Load (psf) Maximum Span Total Live Bpan (in) Load Load (in) Edges Panel Panel Hloeked Span Ratlnp Thlckness or other Edges (in> Support Unbocked 24/0 IS/32,1/2 24 24 60 45 0 5 32/16 15/32 5/8 32 28 55 3 35 3 16 5 6 40/20 19/32,7/8 40 32 40 35 20 48/24 23/32,7/8 48 36 403 353 24 1. There values apply for Structural I and II,C-D Sheathing and C-C grades only. Spans shell bs 1lrnited to values shown because of possible effect of concentrated loads. Edges may be blocked with lumber ar other wpproved type of edge support. 2. Span Rating appears on all panels in construction grades listed iP~ footnote ). 3. For roof live load of 40 psf or total load of 55 psf, decrease spans by 13X or use panel with next greater Span Rating. 4. Plywood edges shall have approved tar~gue and groove ,jainta or shall be supported with blocking, unless 1/4 in minimum thickness underlayrnent or 1 1/2 in approved cellular or lightweight concrete is installed, or finished floor is 25/32 in wood strip. Allowable unifarrn load based on deflection of 1/360 of span is 165 psf. 5. May by 24 in if 25/32 in wood strip flooring is installed at right angles to ,joists. 6. Far ,joints spaced 24 in o. c. plywood aheathinp with Span Ratings numbers 40/20 or greater can be used for subfloors when supporting 1 1/2 in lightweight concrete. 7. In no case shall any roof sheathing be less than 32/16 - 15/32 in. plywood in spans 16 in or more an center. Blocking or clips are required for leas than 19/32 in thick plywood aheathinp. CHAPTER 28 RLUMINUM CON8TRUCTION DELETE AND SUBSTITUTE 2801-GENERAL The quality, design, fabrication and erection of aluminum used structurally in buildings ar structures shall conform to good engineering practice, the provisions of this chapter and other applicable requirements of this code. 2801.1 PERMITS A permit shall be obtained for all aluminum structures and buildings. Rlana and apecificatlons necessary to determine the lacatlon, methods of attachment, materials, power meter location and electrical feed drop shall be submitted with the permit application. All plena and specifications shall be prepared and signed and sealed by a Florida Registered Engineer unless product approval hen been recarnmended as provided for in Section 102.6, Rlternate Methods and Materials. bc2.86ds 27 REV. 8/23/86 2802 STRUCTURAL RLUMINUM CONSTRUCTION The design, fabrication and assembly of structural aluminum far buildings or structures shall conform to Specifications for Rluminurn Structures, Alurnlnum Construction Manual, Section 1, of the Aluminum Association. The use of alunrinurn alloys not listed in the Manual shall be permitted provided their standard of performance is not less than those required in the Manual and the performance is substantiated to the satisfaction of the Building Official. All structural design shall be 1n accordance with Chapter 12 of the Standard Building Code, as amended. 2802.1 All design will be aubJect to the following special provi a i c•na r 1. Sheet metal acrewa may be used only for connections of secondary rnentbers. All primary rnembera will 6e connected with bolt a, pop rivets ar other positive connectors. 2. Sheet metal acrewa may be utilized only in shear. Rny connectors in tension shall be bolted or secured with positive connectors. 3. All connector devices shall be rated by load testing by an approved testing laboratory or as listed in the manufacturers certified published data. 4. Prefabricated wall and roof panels shall comply with all the provisions of Chapter 25 oP this code. 5. All Solid roof systems shell be designed for a mir~irnum 30 psf live load. 6. All buildings and structures shall be designed to resist uplift. In the case of placement on existing slabs and foundations, sufficient information and calculatiorra shall be provided by the design engineer to verify the ability of the slab or foundation to resist uplift leads. 7. Cables are not permissible as required structural support a. 8. Connections to existing walls and/or roofing syaterns shall be supported by specific calculations for each cane to verify the ability of the existing building ar structure to support the additional load. R minimum 2 in nominal wood fascia or sub-fascia properly anchored to the supporting structure shall be required to support an aluntinunt building or structure when connecting to a wood roof aystern. 9. All exterior screen walla shall be set back a minimum of 2 in from the edge of the support slab. 10. Foundations shall be designed in accordance with Chapter 1'3 of the Standard Building Code, as amended. CHAPTER 30 REFERENCED STANDARDS 3001-Referrncrd Standards - AMEND A8 FOLLOWS Standard Designation GR Fire Resistance Design Manual, S1 Edition Section 3003.1.2, Rpp. B, E bc2. BE,da 28 REV. 8/25/B6 APPENDIX 3 MINIMUM STRUCTURAL REOUIREMENT8 FOR ONE RND TWO FAMILY DWELLINGS CHAPTER 3.1 ADMINISTRATION 3.101-TITLE AND SCOPE 3.101.1-TITLE Provisions in the following Chapters shall constitute and be know and may be cited as the MINIMUM 8TRUCTURAL REOUIREMENTB FOR ONE RND TWO FAMILY DWELLINGS as recommended by the Building Code Advisory Board of Palm Beach County, Florida, hereinafter referred to as "this Appendix". 3.101.E-PURPOSE The purpose of this Rppendix is to provide minimum standards far the protection of life, limb, health, property, environment and far the safety and welfare of the consumer, general public and the owners and occupants of residential buildings regulated by this Rppendix. 3.101.3-SCOPE The previsions of this Appendix apply to the construction, prefabrication, alteration, repair, use, occupancy and maintenance of detached one or two family dwellings not more than two atoriec in height, and their accessory structures. Compliance with the requirements of this Rppendix rosy be considered as prima facie evidence of carnpliance with the Standard Building Code. 3.101.4-MINIMUM REtlUIREMENTB 3.101.4.1 DE8I8NER. The minimum raquirernents of this Appendix may be waived when the structure is 'designed by a Florida registered architect or engineer, or when an approved engineered aystern far vertical and horizontal support is used, sub,fect to review for code compliance by the Building Official. 3.101.4.2 MINIMUM LOAD. Thies Appendix 1s based on a rninirnurn connection uplift load of 8S5 lbs. for members spacing of 24 1r.. o. c. and 570 lbs. far members spaced 16 in. o. c. 3.101.4.3 OTHER REOUIREMENTB. It is not the intent of this Appendix to waive any minirnurn requirernenta of the Standard Building Code that are oat mentioned herein. CHAPTER 3.2 FOUNDATIONS 3.201-GENERAL 3.201.1-APPLICATION The provisions of this Chapter shall control the design and construction of the foundation and foundation spaces. Conformity to the specifications herein ar the use of other materials or rnethoda of construction accomplishing the purposes intended by this Rppendix and checked for code carnpliance by the Building Official shall be accepted as complying with this Appendix. 1&21.86ds 1 REV. 8/25/86 3.P02-MATERIALS 3.202.1-STRNDARDB Conformity with the applicable standards specified !n Chapter 30 of the Standard Building Code shall ba evidence that the rnateriala for foundationsr faotingar and foundation walls as set forth in this Chapter are reasonably safe to persons and property. 3.203-FOOTINGS AND FOUNDATION WALLS 3.203.1 DESIGN. All exterior wailer bearing wailer columns and piers shall be supported on continuous solid masonry or concrete footingar or other approved structural systems which shall be of sufficient design to support safely the loads unposed as determined from the character of the soil. Minimum sizes for concrete footings shall be ea sat forth in TABLE-3.201 MINIMUM ALLOWRBLE DIMENSIONS FOR CONCRETE FOUNDATION WALL8 AND FOOTINGS. TABLE 3.E01 MINIMUM RLLOWABLE DIMENSIONS FOR CONCRETE FOUNDATION WALL8 AND FOOTINGS CDNTINUOUB FODTINOS MIN STEEL WALLS DEPTH THICKNESS BOTTOM HEIGHT EXISTING 3" WIDTH GRADE TO CLEAR FOOTING STEEL 80TTOM TO GROUND FRAME 2 STORY 8" 18" 10" 12" 3-NO. 41 FRAME 1 STORY 8"2 16" 8" 12" 2-NO, 4 MASONRY 2 STORY 8"3 20" 10" 12" 3-NO. 51 MASONRY 1 STORY 8"3 18" 10" 12" 3-N0. 41 1. One red in top of footing. 2. 6 in iP of reinforced concrete. 3. ]2 in to provide ledge for ,foist bearing where other than slab floors on grade are used. Where exterior rnanolithic foundations are usedr they shall be a minimum of 14 in. deep frarn the top of the slab to the bottom of the faotinp and a rninirnurn outside finish grade of 6 in. above the bottarn of the foundation shall be required. For interior monolithic faatingr see TABLE-3.201. The above rninirnum sizes apply for soil bearing values of 1700 pounds per square fast or greater. For lesser soil bearing values or for excessive building loader the foundatiana shall be properly designed to suit the particular conditions. Far buildings over one story highr the minimum footing thickness under isolated piers and columns or pasts shall be 12 in. NOTES See Section 1302 Standard Building Coder as amended far soil teat requirements. 1&21.86da 2 REV. 8/25/86 3.203.2-CONSTRUCTION Footings shall be level or shall ba stepped so that both top ar~d bottom of ouch faotinga are level. 3.203.2.1 R11 footings shall be formed unless this requirement is waived by the Huildinp Official. 3.203.2.2 R11 exterior Pootinga except monolithic foundations shall be at least 4 ire. wider on each side than the wall resting on the footing. 3.203.2.3 Postings shall be doweled to existing footing when adding to an exiatinp structure. 3.204-FOUNDATION WALLS 3.204.1-DEBION The minimum allowable design of foundation walla shall be as in TABLE-3.201 MINIMUM ALLOWABLE DIMENSIONS FOR CONCRETE FOUNDATION WALLS RND FOOTINGS. CHAPTER 3.3 CONCRETE BLAHS 3.301.1-TERMITE PROTECTION Termite treatment of soil under slabs on grade under structures !a required prior to placing concrete. 3.301.2-SIZE Except for sidewalks or walkways, slabs on ground or fill shall be a minimum of 3 1/2 in thick and must ba reinforced with a rninirnum of 6 x 6 - 30 x 10 t6 x 6 - W1.4 x W1.4> welded wire mesh, lapped eight 8 in, or its equivalent in reinforcement. CHAPTER 3.4 WALL CONSTRUCTION 3.401-GENERAL 3.401.1-APPLICATION The prc•visior,a of this Chapter shall control the design and construction of lead bearing and exterior walla end partitions for all buildings. Canforrnity with the applicable grading, material, teat, construction and design standards specified in this Chapter and Chapter 30 of the Standard Building Code shall be evidence that walls and partitions are rea$onably safe to persona and property. The use of other materials c•r rnethoda c•f construction accomplishing the purposes intended by this Appendix and checked for code compliance by the Building Official shall be accepted as complying with this Appendix. 3.402-MASONRY CONSTRUCTION The rn nirnurn shall be eight 8 1n. EXCEPTIONr 4 in black walls may be used 1f the 4 in wall is a maximum of 5 ft in length unless reinforced. NOTE( For other type walla, see TABLE-3.201 MINIMUM ALLOWABLE DIMENSIONS FOR FOUNDATION WALL8 RND FOOTINDS, for thickness. 3.402.1-THICKNESS i thickness of exterior walls of hollow masonry unite 3.402.2-WALL SUPPORT Masonry wallc (including walls of plain concrete) shall be supported at such intervalc that the wall panel within the 1R21.86ds 3 REV. 8/25/86 vertical and horizontal supports shall not exceed 256 aquar•e feet in area, provided, however. that for solid masonry walla the distance between vertical supports shall in no case exceed 20 ft, and for hollow walla of masonry ar walla of hollow masonry unite such distance shall not exceed 16 ft. Such vertical and horizontal support shall ba obtained by reinforced concrete colurnns at all corners and at intervals as specified above, and by reinforced concrete tie bearns below each tier of floor or ceiling foists and on top of all walls to form a coping. 3.402.3-COLUMNS Reinforced concrete columns shall be not less than 8 x 12 in and have not leas than 4 5/8 in reinforcing rode with 1/4 in ties spaced 12 in apart. R11 colurnn reinforcing steel shall extend into tie bearns and footings a minimum of 24 diameters or shall have connections designed to develop the full strength of the column reinforcing steel. A column aliall be required ad,facent to any corner opening exceeding 4 ft in width, and adjacent to one aide of any wall opening exceeding 9 ft in width. 3.402.3.1 EXCEPTION FOR-ONE STORY BUILDINGS. The reinforced concrete columns shall not be leas than B x 12 in and have not leas than 2 5/8 in reinforcing rods securely positioned by means of metal ties or spacers. 3.402.3.1.1 In one story buildings only, 8 x 16 in concrete filled colurnn block with 2 5/B in reinforcing rods securely positioned by rneana of wire ties top and bottom may be used in lieu of fanned and poured concrete columns. 3.402.3.1.2 The earner columns may be omitted. 3.402.3.1.3 Calumny in load bearing walls shall be located not further than 6 ft from corners and thereafter at spacing specified 1n Section 3.402.2. 3.402.3.1.4 For non-load bearing exterior walls in one story buildings, colurnns are not required provided the wall panel within the closest vertical and horizontal supports ~ shall not exceed 256 ft square in area. 3.402.3.1.5 When using filled building blocks for calurnna, the black shall be thoroughly wet down irnmadiately prior to pouring. Pea-rock aggregate containing maximum rock size of 3/8 in or pump mix concrete roust be used, with the minimum concrete strength of 2,500 pounds per square in at 28 days. All filled building blocks must be thoroughly rodded when being poured to prevent voids in the pour. The outside of the bottom block of all columns rnuat be broken out prior to pouring to facilitate clean out, wire tying and inspection. 3.402.4-BEAMS 3.402.4.1 Reinforced concrete tlebearna shall not be arnaller than 8 x 12 in, and have not less than 4 5/8 in rods, 2 at the top and 2 at the bottom. Minlmurn lap of steel shall be 30 diameters. 3.402.4.2 Continuity shall be provided at corners by banding 2 outside bare around the corner 18 in ar by adding 2 bent bare which extend 18 in each way from the corners. 1621.86da 4 REV. 8/25/86 3.402.4.3 Tie beam reinforcing steel shall be doweled into the existing when adding to an existing structure. 3.402.4.4 Reinforced concrete coping beams on walla up to 4 ft high shall not be leas than 6 in thick and net less than 48 square in in cross section and shall have not lase than 2 1/2 in reinforcing rode. Buch bearns shall be anchored to the tie beam irnrnediately underneath with reinforced concrete colurnna not smaller than A x 12 in having rrot leas than 4 1/2 in reinforcing rode and placed one column over each column, supporting the tie beam. Coping beams shall be installed along the top of the rakes of gables. 3.402.4.6 Vaida or chases larger than 3 in inside diameter shall not ba permitted in minirnurn size exterior perimeter bearns. 3.40P.6-WATER SYOP Where exterior hollow rnasorrry units bear on a concrete surface, a 1 1/2 in rece$s or another effective water atop, as approved by the Building Official shall be provided to prevent water intrusion. 3.403-WOOD 3.403.1-GENERAL 3.403.1.1 The requirements of thin Section are based on the wall being used in a rectangular prismatic structure a maximum of two story or twenty flue feet in height. The horizontal cornponer~t of roof wind loads and that portion of the wall wind load r•esiated by each wall shall be carried to the foundation by the roof diaphragm action and intersecting shear walla or by other recognized and accepted means. Rllowable shear values for plywood, particleboard and pypaum board diaphraprns can be found in Chapters 17 and 18 of the Standard Building Code, ac amended. 3. 403. l.2 The roof is a symmetrical double eloped roof with a roof span that may vary frarn 14 to 40 feet with a maximum overhang of 4 ft. The roof elope may vary from 2112 to lOr12. The truss/rafter spacing shall not exceed 24 in. 3.403.1.3 The actual weight of the roof system shall equal or exceed 9 psf. The ceiling may be included provided it is supported by the roof system. 3.403.1.4 All load bearing lumber, plywood and particle board shall canforrn to•applicable standards or grading rules and shall be so identified by the grade mark or certificate of inspection issued by an approved grading ar inspection bureau or agency. The grade mark for such load bearing lumber shall provide adequate information to determine the "f" and "E" values. .Approved end ,joined lumber may be used interchangeable with solid sawn rnernbers of the same species and grade.. 3.403.2-LIMITATIONS 3.403.2.1 These requirements apply only to 1 and 2 story one and two family dwellings. Unusual structural conditions may require an architect or engineer to design. 3.403.2.2 All sill plate, stud and top plate lumber shall be No. 3 Southern Pine Surface Dry Moisture Content maximum 19% or other apeciea equal in design values. 3.403.2.3 All woad corning into contact with interior or exterior masonry or concrete Shall be pressure treated or of an approved wood of natural decay reaiatance. Sb21.A6da 6 REV. A/26/86 3.403.2.4 Double top plates are required and they rnust 6e ,joined together to act as one top plate 3 in. thick. 3.403.2.3 All anchor/connectors used shall be recomrnended for approval by the Southern Puilding Code Congress, Tnt. 3.403.2.6 The nail slzea specified in this Code are based on the special Haile recornrnended by the anchor/cormector manufacturers that -have been recomrnended for approval by the Southern Nuilding Code Congress, Int. 3.403.3-WALL UBINO 2 X 4 NOMINAL DIMENBION WODD MEMBERS All wood shall have nominal 2 x 4 dimensions minimum. This wall may only be used in nominal 8 ft. high walls, maxirnum. 3.403.3.1 SILL PLATE The concrete foundation shall be finished to provide a true and even bearing surface for the sill plate. Sill anchors shall be placed at ewch stud and shall be a minimurn 18 gauge thick galvanized steel and be ernbedded in the concrete foundation 4 in. with a hook on the end. The anchor shall be fastened to the sill or to the stud with a minirnurn of 4 - 8d Haile placed as recommended by the anchor manufacturer. 3.403.3.2 STUDS 2 x 4 etude shall be placed a maxirnum 16 in. an center. 3.403.3.2.1 Studs shall be a gauge galvanized steel anchors in each wood mernber) or 4 8d Haile placed as recarnrnended by EXCEPTIONS These anchors foundation anchors required the stud. btached to the sill plate with 2 20 fastened with a minirnurn of 8-6d (4 (2 in each woad member) galvanized anchor manufacturer. are Hat required when the sill to by Section 3.403.3.1 •re fastened to 3.403.3.2.2 5tuda shall be attached to the double top plate with 2 20 gauge galvanized ateei anchors fastened with a minirnurn of 8-6d (4 in each wood mernber) or 4 - Bd (2 in each wood member) galvanized Haile placed as recarnrnended by the anchor manufacturer. 3.403.3.2.3 Alternate Studs shall be attached to the double top plate with an 78 gauge x 1 1/8 in wide galvanized steel strap faater~ed with a minimurn 4 iOd galvanized steel Haile in each mernber. EXCEPTIONt These anchors are not required in one story construction when the truss/rafters are paaitioned over the studs, and anchored as required by Section 3.°SO1.P.2.7.1. and in two story construction when the first and second story studs are vertically aligned and anchored as required by Section 3.403. 6. 3. 1. 3.403.4-WALL USING 2 X 6 NOMINAL DIMENSION WODD MEMHERB All wood shall have nominal 2 x 6 dimensions minimum. This wall may be used in a nominal 70 ft, high wall, maxirnum. 3.403.4.1-SILL PLATE 3.403.4.1.1 Anchors Concrete foundation shall be finished to provide a true ar~d even bearing surface far the sill plate. 8i11 anchors shall be placed at each stud, and shall ba a minimum 18 gauge thick galvanized steel metal and be ernbedded in the concrete foundation 4 in, with a hook. The anchors shall be fastened to the sill or to the stud with a rnlnimurn of 4 iOd galvanized nails and placed as recommended by the anchor manufacturer. 1d21.86ds B REV. 8/25/86 3.403.4.1.2 Alternate Anchor Bolt Connection Nut - steel nut shall be supplied to fit bolt by bolt nranufact urer. 3.403.4.1.2.1 Material Specifications Bolt - nominal 1/2 in diameter steel A307. Washer - steel A36, 3 in x 3 in x 1/4 plate with 9/16 in centered hole. 3.403.4.1.2.2 General Application Bolts shall be placed a maximum of 28 in an center. The maximum hale diameter in the sill plate shall be 5/8 in. When splices are necessary in the sill plate, a bolt shall be placed a maximum of 6 in from each side of the splice and also between the splice and the adjacent stud. A bolt shall be placed a maximum of 12 in from each corner, each offset wall and from each aide of a doorway. 3.403.4.1.2.3 Foundation Wall Application Rnchor bolts, material specifications as in Section 3.403.4.1.2.1, 28 in o. c. shall be anchored to the cap beam in the following mannerr Anchor belts shall be embedded in a cap beat depth of 8 in with a minimum oP 1 No 7 reinforclnp rods. The cap beam shall then more than 4 ft on center with a minimum extending from the footlnp to the cap beam filled with concrete or grout, n tl or ba of in iat has a rninirnurn 2 No 5 steal anchored at not 1 No 5 dowel a cell solidly 3.403.4.2 STUDS 2 x 6 studs shall be placed a maximum 24 in or. center. 3.403.4.2.1 Stud• shall be attached to the sill plate with 2 20 gauge galvanized steel anchors fastened with a rninirnurn 8 6d (4 in each wood member) galvanized Hall placed as recommended by anchor rnanufecturer. EXCEPTIONS Theca anchors are not required when the sill to foundation anchors required by Section 403.4.1.1 are fastened to the stud. 3. 403. 4. 2.P Studs shall be attached to the double top plate with 2 20 gauge galvanized steel anchors fastened with a rninirnurn 8 6d (4 in each wood member) galvanized nails placed as recommended by the anchor rnanufecturer. 3.403.4.2.3 Alternate Studs shall be attached to the double top plate with a 18 gauge x 1 1/8 in wide galvanized steel strap fastened with a rninirnurn 4 IOd galvanized steel nails in each member. EXCEPTIONr These anchors are not required in one story construction when the truss/rafters are positioned over the studs, and anchored as required by Section 3.501.2.2.1.1 and are not required in two story construction when the first and second atary studs are vertically aligned end anchored as required by Section 3.403.6.3.1. 3.403.8-OPENINGS 3.403.3.1 GENERAL Openingc in woad stud walls shall be framed as required in this Section. Full length stud, tap plate, header, cripple and header studs shall be fastened to each other in aurh a manner that will enable them to act together, maintaining vertical alignment and full end bearing. 3.403.3.2 HEADER Refer to Section 1707.3 in the 1986 arnendrnent to the Standard building Code far header rnaterlal and size. 1321.86da 7 REV. 8/25/86 3.403.5.3 FULL LENGTH STUD A stud that is required to be placed between an opening header and the double top plate. 3.403.3.4 CRIPPLE STUD Cripple stud is the partial stud placed between an opening header and the double top plate. Intermediate cripple studs shall be spaced the same as the full height studs. 3.403.5.3 HEADER STUD Header stud is the wood rnernber that supports each end of an opening header. Header stud size shall be the same as the cripple stud above it. 3.403.5.6 LORD BEARING EXTERIOR WALL OPENIN08 3.403.5.6.1 Full Length Stud Refer to Section 3.403.3.2 for anchor to sill and top plates. 3.403.5. 6.P Cripple Stud The end cripple studs that wra over th• header studs shall be a minirnurn 2 x 4 for a <6 ft opening or a minimum 4 x 4 for a >6 ft opening. The 4 x 4 may be 2 2 x 4 if fasteners can ba placed in the center of the 1 1/2 in stud thickness. Anchor cripple stud to header and double top plate carne as required far full length stud 8actlan 3.403.3.2. 3.403.5.6.3 Header Btud Header stud size shall be the same as the cripple stud above it. Anchor header stud at base with galvanized steel anchors and straps embedded in the concrete foundation 4 in with a hook. Anchor the top of the header stud to the double top plate with galvanized steel straps as requlred by TABLE-3.403 ANCHORS REQUIRED FOR LORD HERRING WALLS. TABLE^3.403 ANCHORS REOUIRED FOR LDAD BEARING WALLS HERDER SPAN BABE ANCHDRI iFTI 0-62 18 ga - 1 1/8 in wide 4-lOd nails in each strap. Twa straps or equal are required. >6-122 18 ga - 1 1/8 in wide 4 - lOd nails in each strap. Three straps or equal are required. >12-162 18 pa - 1 1/B in wide 4 - lOd nails in each strap. Four straps or equal are required. 1. All straps/base anchors are to ba foundatic.n 4 in with a hook at the end. 2. 1 full length stud requlred each aide TOP RNCHOR STRAP IB ga - ! 1/18 in wide 4-lOd nails 1n each strap. Two straps or equal are required. 18 ga - 1 1/8 in wide 4 - lOd nails in each strap. Three straps ar equal are required. 18 ga - 1 1/8 in wide 4 - SOd Haile in each strap. Four straps or equal are required. embedded in the concrete of the opening. 3.403.5.7 GABLE/HIP WALL EXTERIOR OPENINGS Header span to be a maximum of 16 ft. This Section applies only to gable walls and walls supporting hip jacks nut longer then 9 ft. 3.403.3.7.1 Full Length Stud 1 full length stud is required at each end of the opening header. Bee Section 3.403.3.2 far connection requirements 3.403.5.7.2 Cripple Stud Cripple studs shall be a 2 x 4 rninirnurn. Anchor cripple studs as required by Section 3.403.3.2 for full length studs. 1&21.86da 8 REV. 8/25/86 J ~ ' 3.403.3.7.3 Header Stud Header stud shall be one 2 x 4 for net rnore than a 6 ft opening and shall be 2 2 x 4~s far rnore than a 6 ft opening. Anchor header stud at base with one galvanized steel strap SB ga. 1 1/8 in wide or equal embedded in the concrete foundation 4 in with a hook. Fasten the strap to the stud with 4 lOd nails. Anchor the top of the header stud to the double top plates with one 18 ga. 1 1/8 wide galvanized steel strap. Fasten the strap to each rnember with 4 lOd nails. 3.403.6-TWO STORY CONSTRUCTION 3.403.6.1 tlENERRL The first story and the second story walls must be connected so that the roof and wall wind leads are carried to the foundation. 3.403.6.2 WOOD DIMENSIONS The wall woad frarning mernber dimensions shall be determined by the height of the wall as limited by Section 3.403.3 and 3.403.4. 3.403.6.3 CONNECTYON REgUIREMENTB 3.403.6.3.1 Studs To Stud Aligned Vertically The lower- stud shall be connected to the upper stud with a 1B gauge x 1 1/8 in wide galvanized steel strap fastened with a minimum 4 lOd galvanized steel nails in each stud. The lower and upper flours studs must be aligned vertically. galvanized steel nails in each plate. 2. The connections frorn the studs to bottom and top platen for bath the first and second story studs shall be as required by Sections 3.403.3.2.2 and 3.403.4.2.2. 3.403.6.3.2 Studs Not Aligned Vertically 1. The second floor bottorn plate shall be connected to the first flaor top plate with a SB gauge x 1 1/8 in wide galvanized steal strap fastened with a minimum 4 - SOd 3.403.7-SPACING AND BRACINtl 3.403.7.1 Hracing of extericr stud walls shall be as required by Section 1707.2 of the Standard Building Code, as amended. 3.403.7.2 Sheathing shall be applied on all exterior wood frame walls. 3.403.7.3 Clearance between wand siding and earth an the exterior of a building shall be net less than six 6 in. R11 aiding shall be,inatalled in accordance with the manufacturers specifications. CHAPTER 3.5 ROOF CONSTRUCTION 3.501.1-GENERAL All wood roof rnernbers shall be securely fastened to the exterior walls with approved anchors. Shaw rafters in save overhangs must be extended inside of the supporting members approximately the same distance as the cantilever extends outside and roust be securely fastened to the rosin roof frarning rnernbera. Overhangs at gable ends a maximum of 6 in are permitted without supporting structural rnernbers. 3.$01.2-ANCHORAGE 3.301.2.1-MASDNRV CONSTRUCTION 3.301.2.1.1 Hearing Walls Anchor each trues/rafter at each er~d with a 1 1/8 in wide, 18 gauge galvanized steel strap. The strap ib21.86ds y REV. 8/25/86 ~' ~ ~ shall be embedded in the cancrete beam with a hook. Fasten the strap to the truss/rafter with a minimum of 2 16d galvanized nails, bend the straps over the top chord and fastened to the aide of the top cord with 1 16d galvanized steal nail. The woad truss/rafter shall be separated from the concrete bearn with a moisture barrier. 3.301.2.1.1.2 Altrrnat• Top Plat• Bolted 3.301.2.1.1.3 Material Specifications Bait - Nominal 1/2 in diameter steel A307 Washer - R36 steel, 3 in x 3 in x 1/4 in plate with 9/16 in centered hole. Nut - Steel nut shall be supplied to fit the bolt by the ball manufacturer. 3.301.2.1.1.4 Application The plate shall be constructed of 2 pressure treated 2 x 6's. Boltg shall be placed a maximum of 48 in on center. The maximum bolt hole diameter in the top plate shall be S/8 in. When splices era necessary in the plate, a bolt shall be placed a maximum of 6 in from each side of the splice. A bolt shall be placed a maximum of 12 in from any end of the plate. Anchor truss/rafter to the bearn plates per Section 3.301.2.2.1.2 3.301.2.1.2 Oabl• Ends The roof system shall be fastened to the concrete bearn to resist wind uplift and lateral wind pressures. R minimum 2 x 4 PT wood plate shall ba bolted to the concrete beam, 4 ft. on center with 1/2 J bolts ar equal. The plate shall be positioned on the bearn so that it bears against the inside face of the battam chord of the gable trues. Nail the bottom chord to the wood blocking with 16d galvanized steel Haile, 2 x 4 lateral braces Prat runs) laid flat, 8 ft. on canter, shall be nailed with 2 16d galvanized steel Halls to the tap of the bottom chord of each oP the 7 trusses that the braces cross or be fastened to the closest girder truss. 3.301.2.2-WOOD FRAME CON8TRUCTION 3.502.2.2.1 Bearing Walls 3.301.2. 2. !. i. Truss/Rafter Over Stud The rninimurn anchor ahal l be 1 1/8 in wide, 18 gauge galvanized steel strap. Fasten the strap to the stud with 4 iOd galvanized steal nails and to the truss/rafter with 2 16d galvanized steel. nails, bend the strap ever the top chord and .fasten to the side of the tap chord with 1 16d galvanized steel nail. 3.301.2.2.1.2 Truss/Rafter Not Ovrr Stud The rninimurn anchor shall ba a 1 1/8 1n wide, 18 gauge galvanized steel strap. Fasten the strap to the double top plate with 4 lOd Haile and to the truss/rafter with 4 IOd galvanized steel Haile, bend the strap over the top chord and fasten to the side of the top chard with 1 IOd nail. 3.301.2.2.2 Oable Ends A 2 x 4 laid flat shall be nailed to the top of the tap plate with 16d galvanized nails staggered 4 in on center. The plate shall be positioned so thwt the edge bears against the inside face of the bottom chord of the trusa~to the blocking with 16d galvanized nails. u.n1 Y. e:.\eb 2 x 4 lateral braces (rat runs) laid flat, B ft. an center shall be nailed with 2 - 16d galvanized nails to the top of the bottom chord of each of the 7 trusses that the braces cross or be fastened to the closest girder truss. 1&21.86da 10 REV. 8/25/86 3.301.3-SHEATHING 3.301.3.1 In no case shall plywood roof sheathing be less than 32/16 span rating 18/32 in thick on spans 16 in or more on center. Blocking or clips are required for less than 19/32 in thick plywood sheathing. 3.301.3.2 Particle board shall not be used as roof sheathing 3.301.4-ROOF COVERING Far roof covering requirements sae the Palrn Beach Countywide Standard for the Installation of Roof Coverings. 3.301.3-ATTACHMENTS TO ROOF SYSTEM A minimum 2 in nominal wood fascia or sub-fascia properly anchored to the supporting structure shall be required to support an aluminum building or structure when connecting to a wood roof cyst ern. CHAPTER 3.6 -PORCH CONSTRUCTION 3.601.1-GENERAL This Chapter is for structural requirements only) all other sections of this Rppendix shall apply. The requirements of this 6ection are based on roof projection from the supporting house wall of a maximum of 14 ft. including any overhang. 3.601.2-FOUNDATION Each post shall concrete psd with A nominal 4 in constructed with a of the poet pads. No 4 rebar contanw be supported by a 30 in x 30 in x 12 in deep No 4 rebara placed at 6 in on center each way. monolithic concrete floor slab shall be 8 in x 12 in thickened edge bearing on the top The thickened edge of the slab shall contain 1 qua. 3.601.3-POSTS/COLUMNS Support pasts/calurnna shall be a minimum 3 in structural steel ar aluminum or 4 in x 4 in No. 3 Southern Pine Surface Dry Moisture Content maxlrnurn 19% ar ether lumber species equal in design values. The support poste/columns shall be placed at all earners and at a maximum of 10 ft. on center under any load bearing beams. 3.601.4-BEAMS The lead bearing beam shall be a minimum 4 in x 30 in wand beam or equal of No. 3 Southern Pine SF MC 19% or other lumber species equal in design values. Load bearing beams of ether rnateriala shall be designed by a Florida Registered Engineer. 3.601.3-RAFTERS Wc.oden roof rafters shall be sized as required by Chapter 17 of the Standard Building Code, as amended. 3.601.6-CONNECTIONS/ATTACHMENTS 3.601.6.1 RAFTERS The roof rafter6 shall be attached to the house wall as is required in Chapter 3 of this Appendix for roof trucaes/rafters. 3.601.6.2 POBTB/COLUMNS The post/column shall be anchored at the base with minimum 12 ga past anchor embedded in the concrete foundation a minimum of 6 in with 2 i/2 in bolts though the pact /co 1 urnn. EXCEPTIONS R metal poet rosy be embedded in the concrete foundation pad with 1 12 in long 1/2 in red through the goat into the concrete. The past/column cap anchor connector shall be 11021. 86da 11 REV. 8/23/86 a minimum 12 pa with 2 1/2 in bolts through both the paBt/column and the beam. EXCEPTIONS Far metal posts the cap anchor rosy be welded to the top of the past/column. All connectors shall be rated for 2800 pounds uplift. ' 3.601.6.3 ATTACHMENTS TO THE ROOF SYSTEM A minimum 2 in nominal wood fascia or sub-faaCla properly anchored to the supporting structure shall be required to support an alurninurn building or structure when connecting to a wood roof syatern. 1821.B6ds 12 REV. 8/28/86 r ATTACHMENT NUMBER 1 REV.B/25/86 This attachment is intended to provide a reference to certain sections of Florida Statutes which outlines specific requirernenta that pertain to this Cods. F.B. CHAPTER 471, in part <2) The following persons are not required to register under the provisions of as. 471.001 - 471.039 as a registered engineers (i) Any electrical, plumbing, air-conditioning, or mechanical contractor whose practice includes the design and fabrication of electrical, plumbing, air-conditioning, or mechanical system, respectively, which he installs by virtue of a license issued under chapter 489, under part 1 of chapter 833, or under any special act or ordinance when working on any constructiarr pra,fect whichr 1. Requires an electrical or 'plumbing or air-conditioning and refrigeration system with a value of 180,000 ar less. and a. Requires an aggregate service capacity of 600 amperes (240 volts) or lase on a residential electrical system or 800 amparea (240 volts) or less on a commercial or industrial electrical system( or b. Requires a plumbing system with fewer than 280 fixture units( or c. Requires a heating, ventilation, and wir-conditioning system not to exceed a 18-tan-per-system capacity, ar if the project is designed to accommodate 100 or fewer persons( or 2. Ir less than 8,000 square feet in area and is designed far public assembly. F.B. CHAPTER 481, !n part (1) No person shall be required to qualify as an architect in order to make plans and specifications for, or supervise the erection, enlargement, or alteration of~ (a) Any building upon any farm far the use of any farmer, regardless of the cost of the buildlnp( or (b) Any one-family or two-family residence building, townhouse, or domestic outbuilding appurtenant to any one-family or two-family residence, regardless of coat( or (c) Any other type of buildlnp costing Less than (25,000, except a schaal, auditarlurn, ar other building intended far public use. F.B. CHAPTER 553, in part (6) No permit may be issued for any building construction, •er-action, alteration, repairs, ar addition unlsaa the applicant for such permit provides to the enforcing agency which issues the permit any of the following documents which apply to the construction for which the permit is to be lasuedr (a> Electrical docurnenta for any new building or addition which requires an aggregate service capacity of 600 amperes (240 volts) or more on a residential electrical system or 800 amparea (240 volts) or mare an a commercial ar industrial electrical system and which cost more than 160,000. (b) Plumbing documents for any new buildlnp or addition which requires a plumbing system with more than 280 fixture unite or which cost more than tS0,000. lc) Fire sprinkler documents for any new building or addition which includes a fire sprinkler system which contains 50 or more sprinkler heads. bc4. at t 1 .~ . id> Heating, ventilation, and air-conditioning docurnents far any new building or addition wMlch requires more than a 18-ton- per-ayctem capacity, which is designed to accommodate 100 or more persona or for which the system costa more than (50,000. Thies paragraph does not lncludo any document for the replacement or repair of an existing system in which the work does not require altering- a structural part of the building or for work on a residential one-family, two-family, three-family, or four-farnily structure. (e) Any specialized rnechanical, electrical, or plumbing document for any new building or addition which includes a medical pas, oxygen, steam, vacuum, toxic air filteration, halon, or fire detection and alarrn system which coat mare than (5,000. No such docurent shall be valid unless a profeaaional engineer who poaaesses a valid certification of registration has signed, dated, and atarnpad such document as provided in a. 471.025 bc4. att 1