THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
CONTENTS
Page 1
A INTRODUCTION 2
• FLOOR PLAN
B BUILDING DESCRIPTION 3
• PICTURES 4
C PROBLEMS AND VIOLATIONS 5 & 6
1. STANDARD BUILDING CODE
2. ENERGY CODE
3. FIRE DISTRICT
4. ADA
D USERS 7
E OPTIONS 8 & 9
F ATTACHMENTS
1. MEMO -KELLY TO HOGARTH -AUGUST 1, 2000 - 1 PAGE
2. MEMO - DENISON TO HOGARTH - 10/04/99 - 2 PAGES
3 FACILITY RENTAL GUIDELINES - 3 PAGES
a
'.e
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
INTRODUCTION
THIS REPORT WAS PREPARED BY R. M. ARSENICOS ,ARCHITECT.
THE MEMO BY DENNIS KELLY, VILLAGE MANAGER, DATED AUGUST 1, 2000 OUTLINED THE
SCOPE OF THIS REPORT. 1 WAS NOT ABLE TO ESTABLISH THE MAINTAINANCE COSTS.
i HAVE DISCUSSED ALL THE OTHER TOPICS LISTED.
I WAS THE ARCHITECT FOR THE NEW ANCHORAGE PARK RECREATION BUILDING. IT WAS
MY UNDERSTANDING THAT ALL OF THE FUNCTIONS THAT WERE HELD IN THE HERB WATT
RECREATION BUILDING WERE TO BE MOVED TO THE NEW FACILITY, AND THE HERB WATT
BUILDING WAS TO BE REMOVED. SINCE IT WASN'T TORN DOWN, IT'S EASY TO
UNDERSTAND THAT PEOPLE WOULD ASK IF IT COULD BE USED, AND IT WAS USED. EVEN
WITH ITS MANY PROBLEMS, IT IS WELL LOCATED AND THE USAGE IS FREE TO SOME OF
THE USERS.
AFTER MY INVESTIGATION, i HAVE REACHED THE CONCLUSION THAT IT WILL BE MY
RECOMMENDATION TO REMOVE THE HERB WATT RECREATION BUILDING.
i
I GL
STOR Ii
ACTIVITY RM- _ _ _ -
CL
-- ~
(.. ~ _i ~
KITCHEN I~ i
_ '
`~~ C-~ I
W _ M
`~ ~~.
. ~I
L - - - - ! - - - - - - -~I--
0 . . 5 10 15 ~ --N
• FLOOR PLAN SCALE IN FEET
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
BUILDING DESCRIPTION:
The original building (the north half} is about thirty five years old. The south half was built about five
years later. It is wood construction, wood studs and wood trusses. The exterior siding is wood
lapped siding. The roof is low slope (3 in 12 ~. ) with a painted mineral surfaced weatherproof
surface. The ceiling is insulated. The exterior walls are not insulated. The floor is resilient tile, it
may be asphalt. It is on a monolithic concrete floor slab that has thickened edges at the perimeter.
The interior wall surfaces are painted drywall. The ceiling is a 2 x 4 lay in accoustical the ceiling
which was installed just below the original drywall ceiling. At that time the batt installation was
added. There are four ceiling mounted fans, independently controlled. The building is air
conditioned, but it does not work. There is one main activity room, containing 1,174 sf ,code allows
the maximum occupancy to be 78 people. There is a food service room (kitchen) with a pass through
to the adjacent multipurpose room. There are also two multi person toilets (small ), one interior
storage closet, one exterior storage closet, and an added storage space for lawn equipment At the
north end, there is a fenced area containing the air conditioning condensing unit. At the south end a
sprinkler well and pump were added. There is an overhead electrical service of 150 amps,
single phase.
a
" THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
'.:~..
~~
~, . _ ~ -~'
~~- :c/ _- _ - --
~FNK ~ *,r^rs1t~' ;P .y _ _ a , ,.4 ~yyay * _:tia ~ / ~,~~ ' • ~ , ~yr~..r \~ ~y r
~~..A. 6 e tin fSY~'~+.~4 ~~_~ ~ ~ °o
~~ - ~.-N+i ~ ., ~ ~J ~ r f ~i,'x~ 4•'tr~~ i 7' ~r'r ' y'4~ ~~ ~,.~5r ~W ~~' ~ 7 t,~. a ~s.~'v'i 9 `
ti6 ~ ~ r~ 7 a ~. +1 c~ ~ f~:3w '*7~ .. ti~ ~. -, x ,fit, R•r}~h>•. ^ a„p ~~
r. ,~5 ~ w ,1:aa y.~~ .P~ 'b .d. %^A"2~ t ~~a~~U> ~' a. ,;.p~..
p ~~,~y A1, ,~rr may' t r
I e66:W,[~.i~'Jr~°b`.a9L:~~t.. ~... oN~iYtr~H~•. T{.1~n .. .x^3'~l~.a~-Cq:'~a6ar~~;i d~y.• T~4^.?Yhr. _....~
J~'~F
~'Y
_ %~
~~~~
'~1 xa:~~? a y.
d s ' w ~ { "'mow _. .. ' ~~~~~~ 4~d~rt
~ ~ ~ „~.
"aa
LL
~~ .. n I~Q
', -~ ~. ~ ~ ~ ^ ~ ~ ~r
~s .,, ~~-.:~
/~
~F. ~ ~
1
N.
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
PROBLEMS
i
GENERAL AGING
ROOF LEAK AND CEILING DAMAGE
WEST SIDE - EARTH IS WASHING AWAY
FROM UNDER THE BUILDING
TOILET NOT WORKING
OTHERS NOT PICTURED
AIR CONDITIONING IS NOT WORKING
TOILETS - DO NOT HAVE THE REQUIRED
NUMBER OF TOILET FIXTURES AND
THEY ARE NOT ADA ACCESSIBLE
LIGHTING -FOUR OF THE SURFACE
MOUNTED FIXTURES ARF NnT WORKING
._ , :~
" ~-~ `
b
0
k'id': .-_ .. ~
~> - ~
a
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
PROBLEMS CONTINUED
STANDARD BUILDING CODE
OCCUPANCY CLASSIFICATION
BUILDING SIZE
CONSTRUCTION TYPE
EXISTING BUILDING
FLORIDA ENERGY CODE
ASSEMBLY - GROUP B =LESS
THAN 100 PEOPLE
1174 SF 1 15 SF = 78 PEOPLE MAX
1940 SF GROSS /ONE STORY
TYPE VI -UNPROTECTED
NO LONGER LEGAL TO BUILD THIS
BUILDING TYPE IN THE FIRE DISTRICT.
"THE BUILDING OFFICIAL SHALL
DETERMINE THE EXTENT TO WHICH THE
EXISTING SYSTEM SHALL BE MADE TO
CONFORM TO THE REQUIREMENTS OF
THE TECHNICAL CODES FOR NEW
CONSTRUCTION". -SEE 3401
REQUIRES A BUILDING TO CONFORM TO CERTAIN STANDARDS.
BUILDING ENVELOPE - NO INSULATION IN THE EXTERIOR WALLS
R 19 RECOMMENDED
INADEQUATE INSULATION AT ATTIC ~`
R 30 RECOMMENDED
WINDOW SHADING -SHIELDED OR TINT APPLICATION RECOMMENDED
FIRE DISTRICT
APPENDIX F (SECTION 102) OF THE BUILDING CODE WAS ADOPTED BY THE
VILLAGE AND IT DOES NOT NOW ALLOW ANY BUILDING OF THIS USE AND TYPE
(TYPE VI -UNPROTECTED CONSTRUCTION), TO BE BUILT.
;-
FLORIDA ACCESSIBILITY CODE -VIOLATIONS
1. ALL DOORS ARE TOO SMALL AT 30 " -MUST BE 36".
2. EXTERIOR DOOR THRESHOLD EXCEED THE'/" HEIGHT LIMIT,
3. HARDWARE DOES NOT COMPLY -OPENING & CLOSING FORCE -
LEVER HANDLES ARE REQUIRED
4. RESTROOMS -THEY ARE TOO SMALL AND ARE NOT AT ALL
ACCESSIBLE. THEY DO NOT PROVIDE TURN AROUND SPACE -
THEY DO NOT HAVE GRAB BARS -THE TOILET SEATS ARE NOT THE
PROPER HEIGHT -THE ACCESSIBLE LAVATORIES NEED LEVER
HANDLES -AND MORE.
5. ALARMS -AUDIBLE AND VISUAL ALARMS ARE REQUIRED (ANSI A117.1)
6. SIGNAGE AND DETECTABLE WARNINGS - ADA REQUIRED
C
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
USERS
PRESENTLY THERE ARE ELEVEN GROUPS MEETING IN THE HERB WATT
RECREATION BUILDING, THEY ARE:
NAME
1. STEP STUDY AA
2. POWER SQUADRON
3. POWER SQUADRON -CLASSES
4. YACHT CLUB
5. NPB BAND
6. SEA SCOUTS
7. WOMEN ABROAD
8. OFFSHORE COMMITTEE
9. YACHT CLUB BOARD
10. BOATING SINGLES
11. RIVIERA BEACH AA
DAY OF MEETING SIZE
SUNDAY 10 - 20
MONDAY 20
VARIOUS 20
4T" MONDAY 80 - 110
TUESDAY 14-16
WEDNESDAY 15
1ST WEDNESDAY 25
2ND WEDNESDAY 10
3RD THURSDAY 10
3RD FRIDAY 50
SATURDAY 30
THEY HAVE BEEN OFFERED OTHER MEETING LOCATIONS AND HAVE DECLINED.
THE YACHT CLUB GROUP IS TOO LARGE TO MEET IN ANY OF THE RECREATION
DEPARTMENT FACILITIES.
THE NPB BAND WAS NOT OFFERED ANOTHER LOCATION BECAUSE THE GROUPS IN
ADJACENT SPACES WOULD BE DISRUPTED BY THEIR MUSIC.
NOTE THAT THE RIVIERA BEACH AA IS MOVING TO ANCHORAGE PARK.
C
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
OPTIONS
A. FIX PROBLEMS, VIOLATIONS AND AGING:
• PROVIDE PROPERLY MARKED, SIZED & SIGNED HANDICAPPED PARKING
• ADD FILL & STABILIZE SOIL UNDER BUILDING
• REPAIR ROOF LEAK, APPLY NEW FINISH COAT
• RECONFIGURE RAMP AT FRONT DOOR
• REPLACE ALL 30" DOORS WITH 36" WIDE DOORS
• REPLACE HARDWARE
• REPLACE THRESHOLD -HEIGHT SHALL NOT EXCEED'/z"
• TOILETS NEED TO BE COMPLETELY REDONE
• HALLWAY NEEDS TO BE WIDER, WHICH MEANS THE KITCHEN CABINETS
REQUIRE REWORKING
• PROVIDE SIGNAGE AS REQUIRED
• PROVIDE AUDIBLE AND VISUAL ALARM
• PROVIDE ATTIC INSULATION, PROBABLY BLOWN IN
• PROVIDE EXTERIOR WALL INSULATION, INTERIOR INSTALLATION WOULD
PROBABLY BE LESS EXPENSIVE THAN THE EXTERIOR TYPE ,WHICH WOULD ALSO
CHANGE THE LOOK OF THE BUILDING
• PROVIDE TINTING TO WINDOWS
• REPAIR LIGHT FIXTURES
• REPLACE AIR CONDITIONING
• TEST FOR RAT INFESTATION
• TEST FOR TERMITES
THE BUDGET RANGE TO ACCOMPLISH THE ABOVE ITEMS IS $25,000 TO $35,000.
THE MAJOR PROBLEM THAT CAN NOT BE CHANGED, IS THE PUBLIC USE BUILDING,
OF WOOD CONSTRUCTION (TYPE VI -UNPROTECTED) IN THE FIRE DISTRICT.
r
a
c
.~
THE HERB WATT RECREATION BUILDING REPORT -SEPTEMBER 2000
OPTIONS -CONTINUED
B. REMOVE THE BUILDING
THERE ARE SOME SALVAGEABLE ITEMS IN THE BUILDING .THE COST FOR
DEMOLITION MIGHT BE $4,500. BECAUSE OF ITS AGE, ADD ANOTHER $500,
TO PAY FOR AN ASBESTOS STUDY THAT IS REQUIRED PRIOR TO DEMOLITION.
THE SHUFFLEBOARD COURTS WILL COST ABOUT $3,500 TO REMOVE.
THE BIG QUESTION IS HOW SHOULD THIS SITE BE USED:
• SOD AND LANDSCAPE
• PARKING
• ANEW BUILDING (USE ?)
• OTHER
OTHER CONSIDERATIONS:
• SHOULD THE SPRINKLER WELL ~ PUMP REMAIN
• WHERE WILL THE LAWN EQUIPMENT BE STORED
• WHERE IS THE ELECTRIC POWER SOURCE FOR ANYTHING ON SITE
• OTHER
1 RECOMMEND YOU ALLOW A BUDGET OF $10,000 TO REMOVE THE BUILDING,
SHUFFLEBOARD COURTS AND RESTORE THE SITE.
IT IS MY RECOMMENDATION THAT YOU REMOVE
THE HERB WATT RECREATION BUILDING
~/ ~~
RUDOL H M. ARSENICOS
ARCHITECT
:-