Ordinance 1988-010 FEB Adopts Standard Plumbing Code 1985 EditionORDINANCE N0. 10-88
AN ORDINANCE OF THE VILLAGE OF NORTH PALM BEACH, FLORIDA
1
AMENDING CHAPTER 22 OF THE VILLAGE OF NORTH PALM BEACH CODE, THE PLUMBING
CODE FOR THE VILLAGE, SPECIFICALLY THE STANDARD PLUMBING CODE, 1985 EDITION.
BE IT ORDAINED BY THE VILLAGE COUNCIL OF NORTH PALM BEACH,
FLORIDA.
Section 1. The first paragraph of Section 22-17 of the Village
of North Palm Beach Code is hereby amended by adding the following:
CHAPTER 2
DEFINITIONS
202 - DEFINITIONS OF TEfUiS
LEAD FREE PIPE AND FITTINGS - containing not more than 8.0 percent lead
LEAD FREE SOLDER AND FLUX - containing not more than 0.2 percent lead.
CHAPTER 5
MATERIALS -QUALITY AND WEIGHT
502 - SPECIAL MATERIALS
502.1 LEAD
See Table 500. Sheet lead shall not be less than the following:
1. For safe pans - not less than 4 psf coated with an asphalt paint or
equivalent.
2. For flashings of vent terminals - not leass than 3 psf.
3. Lead bends and lead traps shall not be less than 1/8 inch wall thickness.
4. Any pipe, solder or flux which is used in the installation or repair of
arty plumbing in a residential or non-residential facility providing water
for human consumption, shall be Lead free with not more than 8.0% lead in
pipes and fittings. This does not apply to leaded points necessary for the
repair of cast iron pipes.
Chapter 6
JOINTS AND CONNECTIONS
602 - TYPES OF JOINTS
602.4 - Soldered points for tubing shall be made with approved fittings.
Surfaces to be soldered shall be cleaned bright and all burrs shall be
removed and the tubing shall be returned to full bore. The points shall
be properly fluxed and made with approved solder (See 502.1 (4) and 603.6).
All solder and flux used in the installation or repair of water supply or
distribution systems shall be lead free.
CHAPTER .12
WATER SUPPLY AND DISTRIBUTION
1205 - WATER SUPPLY SYSTEM AND WATER SERVICE PIPING
1
1205.1 - MATERIAL UNDERGROUND - SUBSTITUTE THE FOLLOWING:
1205.1.1 - Materials for underground water supply system and water service
shall be a minimum of Type "M" copper tube, brass pipe, polybutylene (PB)
pressure pipe that meets the following Standards: P.B. - 2110, ASTM - D2666
- 250 PSI @ 73.4 degress and AWWA - C902-78 G-134, all to be installed with
the approved fittings. Schedule 40 galvanized steel pipe may be used only
in areas where the water is not corrosive and with the approval of the
Building Official. Water pipe with more than 8.0% lead shall not be used.
1205.1.2 - Underground piping for lawn sprinklers and irrigation systems
may be 194 Standard Water Tube, CA alloy 122 4later Distribution Tubing that
meets ASTM Specifications, B 447-74 or B 251-72, cast iron pressure pipe,
Schedule 40 galvanized steel pipe, pressure rated 160 PSI PVC or pressure
rated 150 polybuthylene plastic piping.
1205.1.3 - All pipe fittings, solder and flux used in the installation of
water supply systems shall be lead free.
EXCEPTION: Leaded joints may be used for the repair of existing cast iron
pipes.
1210 - WATER DISTRIBUTION PIPE, TUBING AND FITTINGS
1
1210.1.4 - All pipe fittings, solder and flux used in the installation of
of water distribution systems shalt be lead free.
EXCEPTION: Leaded joints may be used for the repair of existing cast iron
pipes.
Section 2. This Ordinance shall take effect immediately upon
passage.
PLACED ON FIRST READING THIS ~y DAY OF JANLIARY 1988•
PLACED ON SECOND, FINAL READING AND PASSED THIS-11TH DAY OF
FEBRUARY
(Village Seal)
1988.
~~ ~~~-~-